40
Reference Manual
00809-0400-4101, Rev BA
Electrical Installations
January 2018
Electrical Installations
4.6.1
Conduit installation
Recommended conduit connections are shown in
.
Figure 4-4. Conduit Installation Diagrams
A. Possible conduit line positions
B. Sealing compound
4.6.2
Power supply
4–20 mA HART (option code A)
Transmitter operates on 10.5–42.4 Vdc at the terminal of the transmitter. The dc power supply should
provide power with less than two percent ripple. A minimum of 16.6V is required for loops with a 250
Ω
resistance.
Note
A minimum loop resistance of 250
Ω
s is required to communicate with a Field Communicator. If a single
power supply is used to power more than one transmitter, the power supply used, and circuitry common
to the transmitters, should not have more that 20
Ω
s of impedance at 1200 Hz.
If all connections are not sealed, excess moisture accumulation can damage the
transmitter. Make sure to mount the transmitter with the electrical housing positioned
downward for drainage. To avoid moisture accumulation in the housing, install wiring with
a drip loop, and ensure the bottom of the drip loop is mounted lower than the conduit
connections of the transmitter housing.
B
A
B
A
Содержание Rosemount 2051G
Страница 2: ......
Страница 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...
Страница 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...
Страница 64: ...56 Reference Manual 00809 0400 4101 Rev BA Operation and Maintenance January 2018 Operation and Maintenance ...
Страница 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...
Страница 89: ......