39
Reference Manual
00809-0400-4101, Rev BA
Electrical Installations
January 2018
Electrical Installations
AMS Device Manager
1. Right click the device and select
Configure.
2. Under
Manual Setup
select the
Security
tab.
3. Within the
LOI
select the
Configure Password
button and follow the screen prompts.
LOI
Figure 4-3. LOI Password
4.5
Setting transmitter alarm
On the electronics board is an alarm switch, reference
for switch location. Follow
the steps below to change the alarm switch location.
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover; cover must be fully engaged to comply with explosion proof requirements.
4.6
Electrical considerations
Note
Make sure all electrical installation is in accordance with national and local code requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN P
TAG
ALARM SAT VALUES
PASSWORD
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
PASSWORD
PASSWORD ENABLE
CHANGE PASSWORD
BACK TO MENU
EXIT MENU
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Содержание Rosemount 2051G
Страница 2: ......
Страница 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...
Страница 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...
Страница 64: ...56 Reference Manual 00809 0400 4101 Rev BA Operation and Maintenance January 2018 Operation and Maintenance ...
Страница 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...
Страница 89: ......