7.3.9
Incorrect level when product surface is above 50%
Symptom
The reported level is incorrect when the product surface is above the 50% level.
Figure 7-9: Symptom
A
B
C
D
A. Level
B. Time
C. Actual level
D. Reported level
Possible cause
A strong double bounce echo is interpreted as the product surface.
Recommended actions
•
Move the transmitter to another position.
Related information
Service and troubleshooting
Reference Manual
May 2021
00809-0200-4480
56
Rosemount 1408A Level and Flow Transmitter