The transmitter can be set to output a switching signal for high and low limits (using the
same pin).
Procedure
1. Under
Menu
, select
Parameter
→
Basic Setup
.
2. In the
Digital Outputs P-n
list, select
PnP
or
nPn
.
3. Select
OUT1 Digital Output
or
OUT2 Digital Output
.
4. In the
OUT1 Configuration
or
OUT2 Configuration
list, select
Digital Output Normally
Open
.
5. In the
DO Control Variable
list, select
Level
or
Volume Flow
.
6. Select
Set Point Configuration
, and then set the alarm parameters as desired.
7. Select
Write to device
.
Related information
5.5.5
Set up the volume flow measurement
Procedure
1. Under
Menu
, select
Volume Flow
.
2. In the
Volume Flow Calculation Method
list, select the preferred method. Choose
from:
•
Linearization table
•
Parshall flume
•
Khafagi-Venturi flume
3. Select
Volume Flow Table/Formula
, and then set the parameters as desired.
4. Select
Write to device
.
Related information
Configuration
Reference Manual
May 2021
00809-0200-4480
34
Rosemount 1408A Level and Flow Transmitter