
7.2.3
General power supply fault – Check availability
Alarm classification
Device status
Failure
Class
Error
Possible cause
Power supply drops below 18 Vdc during transmitter start-up.
Recommended actions
Verify voltage is 18-30 Vdc at the transmitter terminal.
7.2.4
Parameter error – Check data sheet and values
Alarm classification
Device status
Failure
Class
Error
Possible cause
The device has detected a configuration error.
Recommended actions
1. If analog output is used, check Upper and Lower Range Values.
2. If digital output is used, check High and Low Alarm Set Points.
3. If condition persists, restore default settings and reconfigure the device.
Related information
Upper/lower range value
Alarm set points
Restore to factory settings
Reference Manual
Service and troubleshooting
00809-0200-4480
May 2021
Reference Manual
41
Содержание Rosemount 1408A
Страница 6: ...Introduction Reference Manual May 2021 00809 0200 4480 6 Rosemount 1408A Level and Flow Transmitter ...
Страница 12: ...Transmitter overview Reference Manual May 2021 00809 0200 4480 12 Rosemount 1408A Level and Flow Transmitter ...
Страница 89: ...Reference Manual 00809 0200 4480 May 2021 Reference Manual 89 ...