Chapter 3
GFK-3019G
Oct 2019
EGD Machine Adapter
12
Supported Configurations for EGD Machine Adapter (EGD interval update 480 ms)
Publish Interval
(ms)
MFA Max Configured and
Published 4-Byte Variables
VFA Max Configured and Published
4-Byte Variables
1000-1999
350 (one exchange)
1
1050 (three exchanges)
2000-2999
700 (two exchanges)
2450 (seven exchanges)
3000-3999
1050 (three exchanges)
3850 (eleven exchanges)
≥4000
1400 (four exchanges)
5250 (fifteen exchanges)
3.6
Troubleshooting
Before attempting some of these possible solutions, be sure to check that the string for each
of the configurations in the .config and .xml files are valid and not empty. For example, the
IP address should follow the correct format and should exactly match the intended IP
address.
3.6.1
The EGD debug webpage
Configuring and Accessing the Webpage
The EGD Debug Webpage is intended to aid in debugging EGD configuration issues. It can
be accessed using a web browser while the EGD Machine Adapter is running. It provides
information on the configurations, statistics of the messages, details of EGD packets, and
logging messages.
Before accessing the webpage, the following configuration modifications are needed:
1.
Open the file org.ops4j.pax.logging.cfg for editing inside in
<Configuration Template>/configuration/machine.
2.
Add the following lines at the end of the file:
log4j.category.com.ge.ac.pmAdapter=DEBUG
log4j.category.com.ge.ac.pmEgd=DEBUG
log4j.category.com.ge.ac.egd=DEBUG
3.
Save and close org.ops4j.pax.logging.cfg.
After deploying the updated configurations above, access the webpage using the following
URL:
https://<Field Agent IP address>:8443/egd/startup
If running the EGD locally on a PC instead of a Field Agent appliance, access the webpage
using the following URL:
1
Exchanges are fully populated.