User Manual
Section 8
GFK-2958L
May 2021
Commissioning
430
PROFINET Scanner Parameters IO-device Access Point
Figure 263
Inputs Default: Choose whether the RX3i CPU will set inputs from any modules in the
EPXPNS001 module’s remote node
to Off or Hold Last State in the following cases:
•
The EPXPNS001/ EPXPNS101 is not operational or is removed.
•
The EPXPNS001/ EPXPNS101 cannot reach the scanner due to cable or network
configuration issues.
•
The EPXPNS001/ EPXPNS101 is not able to scan the VersaMax module in its remote
node.
I/O Scan Set: Specifies the I/O scan set to be assigned to the EPXPNS001/ EPXPNS101. Scan
sets are defined in the CPU’s Scan Sets tab. The valid range is 1 through 32; the default value
is 1.
PROFINET Scanner Parameters (Media Redundancy Tab)
By default, the EPXPNS001/ EPXPNS101 is not set up for Media Redundancy. If the system
will use Media Redundancy, open the Media Redundancy Tab and select Client.
Figure 264