107
Example of an Suboptimal Module Arrangement
Product
Input data
Output
data
Number of input
registers
Number of
output registers
Remarks
EPXMBE001/
EPXMBE101
0
0
EP-1214
1 Byte
--
1
0
allocated 1 register
EP-4164
--
4 words
0
4
allocated 4 registers
EP-3164
4 words
--
4
0
allocated 4 registers
EP-1214
1 Byte
--
1
0
allocated 1 register
EP-125F
2 Byte
1
allocated 1 register
EP-153F
2 Byte
1
allocated 1 register
Total
8
4
Data Widths of I/O Modules in the Modbus Register Range
Module
Process data
Input
Output
EP-1214
1 Byte
--
EP-1218
1 Byte
--
EP-1318
1 Byte
--
EP-125F
2 Byte
--
EP-12F4
15*(2 Byte, 1 Word)
--
EP-153F
2 Byte
--
EP-2214
--
1 Byte
EP-2614
--
1 Byte
EP-2634
--
1 Byte
EP-2218
--
1 Byte
EP-225F
--
2 Byte
EP-2814
--
1 Byte
EP-2714
--
1 Byte
EP-291F
--
2 Byte
EP-5111
2 DWord, 2 Word
2 DWord, 1 Word
EP-5112
2 DWord, 2 Word
2 DWord, 2 Word
EP-5212
4 DWord, 2 Word
2 DWord, 2 Word
EP-5422
2 Word
2 DWord, 2 Word
EP-5442
2 Word
2 DWord, 2 Word
EP-5324
2
…
64 Bytes
2
…
64 Bytes
EP-3164
4 Word
--
EP-3264
4 Word
--
EP-3664
4 Word
--
EP-3124
4 Word
--
EP-3804
4 Word
--
EP-3368
8 Word
--
EP-3468
8 Word
--
EP-4164
--
4 Word
EP-4264
--
4 Word
EP-3704