User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
289
5.23.3
Specifications EP-5324
Specifications
Description
System data
Data
Process, parameter and diagnostic data depend on the network adapter
used (refer to Section Order and Arrangement of Modules).
Interface
RSTi-EP I/O communication bus
System bus transfer rate
48 Mbps
Digital Inputs
Number
4
Sensor types
Type 1 and Type 3 as per IEC 61131-2
Low input voltage
< 5V
High input voltage
> 11V
IO-Link Interfaces
Number
4
Type
IO-Link as per IEC 61131-9
Transfer rate
4.8 kBaud / 38.4 kBaud / 230.4 kBaud, depending on the connected IO-
Link device
Output current C/Q (in DO mode)
0.1 A
Input type C/Q (in DI mode)
1)
Type 1 and Type 3 as per IEC 61131-2
Output current L+
0.5 A per channel, Total max. 2 A
Line Break Detection
yes
Short-circuit-proof
yes
Module diagnosis
yes
Individual channel diagnosis
yes
Supply
Supply voltage
20.4V
–
28.8V
Current consumption from system current
path I
SYS
, typ.
8 mA
Current consumption from input current
path I
IN
25 mA + sensor supply
General data
Type of connection
‘’PUSH IN’’
Weight
88 g (3.10 oz)
Height
120.0 mm / 4.72" (with release lever: 128.0 mm / 5.04")
Width
11.5 mm / 0.45’’
Depth
76.0 mm / 2.99"
Protection class (IEC 60529)
IP 20
For additional general data, refer to Section
General Technical Data for I/O Modules.
1)
If C/Q is used as digital input, the connected device shall only be supplied via L+ and L- connection of the respective
channel.
5.23.4
Modifiable Parameters for EP-5324
Channel Description
Options
1)
Default
0
… 3
Operating mode
disabled (0) / DO (1) / DI (2) / IO-Link (3)
disabled