User Manual
Section 5
GFK-2958L
May 2021
Detailed Description of I/O Modules
339
5.30.3
Modifiable Parameters for EP-4164
Channel Description
Options
Default
0 - 3
Output range
0 to 20 mA (0) /
4 to 20 mA (1) /
0 V to 10 V (2) /
-10 to 10 V (3) /
0 to 5 V (4) /
-5 to 5 V (5) /
1 to 5 V (6) /
2 to 10 V (7) /
disabled (8)
disabled
0 - 3
Substitute value
Depending on the channels data format (S5/S7
0
5.30.4
Diagnostic Data EP-4164
Name
Bytes
Bit
Description
Default
Error indicator
0
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
0
6
Reserved
0
7
Parameter error
Module type
1
0
Module Type
0x05
1
2
3
4
Reserved
0
5
Reserved
0
6
Reserved
0
7
Reserved
0
Error byte 2
2
0-7
Reserved
0
Error byte 3
3
0-2
Reserved
0
3
Internal diagnostic FIFO full
4
Power supply fault
5
Reserved
0
6
Reserved
0
7
Reserved
0
Channel type
4
0-6
Channel type
0x73
7
Reserved
0
Diagnostic bits per
channel
5
Number of diagnostic bit per channel
0
Number of channels
6
Number of similar channels per module
4
Channel error
7-10
0-31
Reserved
0