62 • MultiFlex CUB-II and CUB-TD I&O Guide
026-1705 Rev 7 06-APR-2010
Appendix A: TD Quick Start
Set Up Motor Room Tem-
perature and Plenum
Temperature Inputs
CUB can have up to four motor room tem-
perature zones, which are pre-associated with
Global Data spare analog inputs 1-4. The default
CUB zone is 1, which associates Motor Room
Temp 1 to all CUBs in Zone 1. For CUBs, the
spare analog inputs must be set up for local only/
degrees fahrenheit, and assigned to an input
board and point.
Note that CUB has the option of getting
motor room temp from an input on the CUB
board itself. If this option is used, the TD board
and point assignment will be overridden. See
Section 6.4.2., Motor Room Temperature Con-
trol
for more information.
Plenum Temperature
Because Global Data Spare Analog Inputs
1-4 are preassigned to Motor Room Temps 1-4,
begin setup of plenum temps with Spare Analog
Input 5. If Spare Analog Input 5 is being used,
begin at the next unoccupied analog input. For
example, if four plenum temps are used, they
will come from Spare Analog Inputs 5-8.
Global Data Setup Example
One 16AI board is needed for this setup
example, which will be Board 1. The 16AI has
Motor Room Temp 1 on Input 1, and the first
plenum temp on Input 9.
To begin programming the CUB-TD, navigate
to the Global Data screen to define Global Data
points. Press
followed by
and
to enter
Global Data Setup.
If using an E2 controller, press
,
(Sys-
tem Configuration),
(Global Data),
(Set-
up) to enter Global Data Setup.
1. Under
S1: Inputs
, arrow down to
Spare Anlg Mode
and set to
Local
Only
. Press
for Look Up menu
(
for Look Up if using an E2).
2. Arrow down to
Spare Anlg EU
and
set to
DF
(Degrees Fahrenheit). Press
for Look Up menu (
for
Look Up if using an E2).
NOTE: This section contains an overview for
setting up TD Control for CUB-II or CUB-
TD. In this section of the manual, the term
"CUB" will be used to mean "CUB-II and, if appro-
priate, CUB-TD."
NOTE: You cannot use Global Data’s
SPARE ANLG 01 through 04 inputs for any
purpose other than motor room temps; they
are predefined. If you need to use some of Global Da-
ta’s “Spare Analog” slots to share values, (plenum
temp) use SPARE ANLG 05 through 08.
Figure A-1 - Global Data Setup Local Only Mode