5.6
Configure the FTP server to download
firmware
Firmware is installed in directory
C:\Inetpub\ftproot\bin\
in a folder with a name for the product
model:
2600
or
2600T
.
Each time a CSI 2600 powers up, it scans its network connection looking for the address
that matches an address stored in internal CSI 2600 memory, and then for firmware at this
directory location. If firmware is found, its version is read and compared to a copy of
firmware stored in internal CSI 2600 memory. If the firmware is the same revision, then the
CSI 2600 boots from its internal copy. If it has a different revision, then the CSI 2600
downloads newer firmware, boots using it, and stores a copy of this newer firmware in
internal memory.
Unless otherwise specified, CSI Machinery Health Monitor systems are pre-configured and
set up during commissioning.
The FTP service must be configured on a computer on the network so that a CSI Machinery
Health Monitor can obtain firmware updates. If an FTP site is not available, the CSI
Machinery Health Monitor boots from the firmware stored in memory. The FTP service is a
Windows Feature that is available but not enabled by default on Microsoft Windows. Refer
to your Microsoft Windows Operating System instructions to enable the FTP Server and set
up an FTP site. These instructions are an overview of the steps to configure an FTP server
for the CSI 6500 on Windows 7 and Windows 2008 R2.
Procedure
1.
Go to
Control Panel
>
Programs
>
Programs and Features
and select
Turn Windows Features on
or off
.
2.
Expand
Internet Information Services (IIS)
and select the following features:
FTP Server
,
FTP Service
, and
IIS Management Service
.
Microsoft Windows configures the services.
3.
Launch Internet Information Services Manager.
To find the program, go to
Start
, type
IIS
in the search box, and select Internet
Information Services (IIS) Manager.
Internet Information Services (IIS) Manager opens.
4.
In the
Connections
pane, expand the computer node, right-click
Sites
and select
Add
FTP Site
.
The Add FTP Site dialog appears.
5.
Complete the steps in the wizard and configure the settings to match the FTP
settings on the CSI Machinery Health Monitor according to the following example.
Software configuration
48
MHM-97453, Rev 1
Содержание Machinery Health Expert CSI 2600
Страница 1: ...User Guide MHM 97453 Rev 1 April 2014 CSI 2600 Machinery Health Expert User Guide ...
Страница 8: ...CSI 2600 back view Figure 2 2 Introduction to the CSI 2600 4 MHM 97453 Rev 1 ...
Страница 12: ...Introduction to the CSI 2600 8 MHM 97453 Rev 1 ...
Страница 26: ...Getting started 22 MHM 97453 Rev 1 ...
Страница 64: ...Software configuration 60 MHM 97453 Rev 1 ...
Страница 96: ...Data types 92 MHM 97453 Rev 1 ...
Страница 100: ...D 2 Internal wiring diagram for the CSI 2600 ...
Страница 106: ...Troubleshooting 102 MHM 97453 Rev 1 ...
Страница 109: ...Index MHM 97453 Rev 1 105 ...