Installation Drawings
139
Figure 147 Wiring specifications, Liebert FS and Liebert Series 610
Wire
No.
Terminal
Designation
Signal
Name
Maximum
Voltage
Maximum
Current
Color
Wire Size
& Type
Maximum
Length
Remarks
From
To
Liebert Series 610 UPS - Cable Group #16 (Flywheel CB IFM) From I1 in UPS Module to TB1 on Liebert FS Module
901 I1-TB1-1 TB1-1 Trip Signal (+)
+24 VDC
100mA
1/C #16 (2.5 mm
2
)
Stranded
500 Ft
(150 M
902 I1-TB1-2 TB1-2
Trip Signal (-)
-24 VDC
100mA
903 I1-TB1-7 TB1-7
Aux Comm
24 VDC
100mA
904 I1-TB1-8 TB1-8
Aux N.O.
24 VDC
100mA
Liebert Series 610 UPS - Cable Group #116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused
Disconnect
914
FBO
TB1-1
Line
120VAC
3.5A
1/C #16 (2.5 mm
2
)
Stranded
500 Ft
(150m)
UPS-
Protected
Auxiliary
Power
Control
915
FBO
TB1-2
Neutral
120VAC
3.5A
916
FBO
TB1-3
GND
120VAC
3.5A
1. Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.
2. Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
3. All external wires furnished by others.
4. N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground
5. All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_S610_Liebert-FS Rev. 01
Содержание Liebert FS Series
Страница 2: ......
Страница 12: ...x ...
Страница 127: ...Installation Drawings 115 Figure 121 Electrical connections ...
Страница 128: ...Installation Drawings 116 Figure 122 Electrical system block diagram ...
Страница 130: ...Installation Drawings 118 Figure 125 Outline drawing Liebert FS cabinet 12 100120 00 Rev 01 ...
Страница 156: ...Installation Drawings 144 Figure 152 Power line diagram ...
Страница 166: ...Auxiliary Backup AC Power Supply 154 ...
Страница 167: ......