Data Collection Module
105
Appendix B.3.3 Datafiles Screen
This screen lists the different files types for viewing and download. There are five files types: F, S, L,
A and D.
•
F
indicates a fast data packet, containing electrical information such as voltages, amps and watts.
•
S
represents a slow packet for measurements collected over a longer period, such as tempera-
tures.
•
L
stands for Log files and these contain information on system modes, statuses and commands.
•
A
indicates an alarm file and will contain information on any Faults or Warnings recorded.
•
D
files indicate a system discharge and allow a user to view the time, duration and amount of Dis-
charge.
Figure 114 Datafiles screen