General System Information
6
Figure 4
One or more Liebert FS units in parallel with one or more battery strings, battery cabinets or
batteries in racks
1.2.1 General Specifications
Table 2
summarizes the technical specifications of the Liebert FS.
For more-detailed technical specifications, refer to
Technical specifications on page 148
.
Table 2
General system specifications
Rated Power Delivery
Dependent upon the duration required;
refer to
Figure 5
Input Voltage (DC)
360 through 600 VDC; > 520 VDC required for 190kW
Output Voltage (DC)
350 through 590 VDC; > 510 VDC required for 190kW
Input Voltage Aux. (AC)
85 VAC – 265 VAC (47-63Hz)
Operating Temperature
-20°C to 50°C (-4°F to 122°F)
Non-Operating Temperature
-20°C to 80°C (-4°F to 176°F)
Dimensions (W x D x H)
63 x 83 x 180 cm (25 x 33 x 71 in)
Total Weight
590 kg (1,300 lb)
Loads
UPS Block Diagram
UPS
DC Bus
AC
DC
DC
AC
Liebert
FS Unit 1
Liebert
FS Unit 2
Liebert
FS Unit N
Utility
Power
Battery 1
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
EMERSON
Network Power
Liebert
Battery 2
Battery N
Содержание Liebert FS Series
Страница 2: ......
Страница 12: ...x ...
Страница 127: ...Installation Drawings 115 Figure 121 Electrical connections ...
Страница 128: ...Installation Drawings 116 Figure 122 Electrical system block diagram ...
Страница 130: ...Installation Drawings 118 Figure 125 Outline drawing Liebert FS cabinet 12 100120 00 Rev 01 ...
Страница 156: ...Installation Drawings 144 Figure 152 Power line diagram ...
Страница 166: ...Auxiliary Backup AC Power Supply 154 ...
Страница 167: ......