Commissioning the Device in E2E
iPro Parameter List • 61
16
iPro Parameter List
Parameter Name
Description
Range
Fan Parameters
FOp
Fan Operation Mode: OnR-OfD-Fan on with refrigeration off
defrost. OnR-OnD-Fan on Refrigeration on defrost. OnF-OfD-Fan on
continuously off defrost. OnF-OnD-Fan on continuously, on
defrost.
OnR-OfD, OnR-OnD, OnF-OfD,
OnF-OnD
FAd
Fan After Defrost: Temperature-Activate after defrost based on Fst,
Fhy. Time-Activate after defrost based on Ftd.
Temperature/Time
FSt
Fan Temp Setpoint
-10-70°
FHy
Fan Temp Hysteresis
1-30°
Ftd
Fan Time Delay
0:00-10:00 minutes
FanAmpOn
Amps required for Fan status to be considered ON
0-60 amps
FanAmpDel
Time delay for status change once amps reach threshold
1-90 seconds
Alarm Parameters
ALU
Maximum control temperature alarm, relative to active setpoint
0-99° above setpoint
ALL
Minimum control temperature alarm, relative to active setpoint
-99-0° below setpoint
AHy
Alarm hysteresis
0-20°
ALd
Alarm delay time before displaying alarm active
0-255 minutes
SHF%
Superheat Control Temp failure-position valve is driven to in the
event of superheat reading failure
0-100%
SCF%
Suction Control Temp failure-position the valve is driven to in the
event of control temperature failure
0-100%
Analog Input Parameters
AIC01
Configuration of Probe 1
Discharge 1-6, Return 1-3, Defrost Term
1-6, Coil Out 1-3, Pressure 1-3, Fan
Amperage, Defrost Amperage
AIC02
Configuration of Probe 2
AIC03
Configuration of Probe 3
AIC04
Configuration of Probe 4
AIC05
Configuration of Probe 5
AIC06
Configuration of Probe 6
AIC07
Configuration of Probe 7
AIC08
Configuration of Probe 8
AIC09
Configuration of Probe 9
AIC10
Configuration of Probe 10
Table 16-1
- iPro Parameter List