![Emerson iPro Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/emerson/ipro/ipro_installation-and-operation-manual_102418038.webp)
30 • iPro Case Controller I&O Manual FM V1.01
026-1738 Rev 1
Note that if the Modbus address or baud rate is changed, the controller must be rebooted.
10.3.4.3. Superheat and Suction
Control-Refrigeration Relay
The management of the refrigeration relay in this mode is the
same as described in
Section 10.3.3.,
Suction Control Mode
.
10.3.5. Defrost Control and Operation
10.3.5.1. Initiation of Defrost
The case controller defrost is managed completely internally by
the case controller and needs no instructions from a supervisory
controller or E2E. The case controller has an internal schedule for
defrost cycles. Based on the start time and the number per day, the
controller will evenly space the defrosts based through a 24 hour
day. For example, if the start time is 0:00 and the number per day
is 4, the controller will schedule 4 defrosts evenly every 6 hours at
0:00, 6:00, 12:00, and 18:00. When a scheduled defrost time is
reached, the controller starts the defrost cycle and drives the EEV
valves to the percentage defined by
SHDef%
and drives the
EEPR valve to the parameter
SuctionDef%
. The defrost relay is
switched to ON and the refrigeration relay is switched to OFF.
10.3.5.2. Master/Slave Defrost of a Lineup
If the case controller is a device that is part of a common
refrigeration circuit lineup, the controller is considered either the
lead/master case or a slave case. In a lineup of masters/slaves the
master manages defrost for the entire circuit. When the scheduled
defrost time is reached for the circuit, the master controller will
start defrost (if no lockout is present) and communicate to all slave
controllers to start a defrost cycle. Once in defrost, all case
controllers will execute defrost and terminate according to their
own individual termination settings. The master controller will be
notified when each slave controller terminates its defrost cycle.
A detailed description of defrost termination is found in
Section
10.3.5.4.,
Defrost Termination
and
Section 10.3.5.5.,
Wait Mode
.
10.3.5.3. Defrost Operation of Relays and
Valves
Whenever the defrost cycle begins, the case controller drives the
electronic valves to their respective defrost positions as defined by
parameters
SHDef%
and
SuctionDef%
. The refrigeration
relay is driven to the OFF position and the defrost relay is
switched to ON.
The evaporator fan operation during defrost is governed by the
parameter
FanOp
. The options are shown in the table below:
10.3.5.4. Defrost Termination
The defrost termination is managed locally by the case controller.
The termination options are: temperature and time.
Temperature
-When temperature termination is selected, the
terminating sensor must be specified by parameter
dTS
: the
options for sensors to select are: defrost termination, discharge air,
or coil outlet. Once the combined termination value reaches the
defrost termination setpoint, the defrost cycle is terminated and
the system enters Drip mode (if drip time is programmed).
Following Drip mode, the system enters Wait mode. Wait mode is
only entered if the controller is a part of a master/slave lineup
network. If there is no master/slave network, wait mode is
skipped. During Temperature Termination mode, the case
controller is always monitoring maximum time, and if the
maximum time duration is ever exceeded, the defrost is
terminated immediately.
Time
-When time termination is selected, the defrost cycle runs
for a time value only and then terminates. No temperature sensors
are considered. Following the time termination, the case
controller performs drip time if applicable and then enters Wait
mode.
FanOp Parameter Values
Description
OnR-OffD
Fan relay is on during
refrigeration and off
during defrost cycle
OnR-OnD
Fan relay is on during
refrigeration and on
during defrost cycle
OnF-OffD
Fan relay is on
continuously and off
during defrost cycle
OnF-OnD
Fan relay is on
continuously and on
during defrost cycle
Table 10-6
- Evaporator Fan Operation During Defrost
Содержание iPro
Страница 1: ...iPro Case Controller Installation and Operation Manual FW Version 1 01 026 1738 Rev 1 ...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 78: ...70 iPro Case Controller I O Manual FM V1 01 026 1738 Rev 1 17 Appendix iPro Connection Detail ...
Страница 79: ......