66 • iPro Case Controller I&O Manual FM V1.01
026-1738 Rev 1
EEPR_IntervU
EEPR - Interval of updating-The time between updates for the output
position of the valve
0-60 Seconds
EEPR_MaxP
EEPR - Max Opening Percentage
0-100%
EEPR_MinP
EEPR - Min Opening Percentage
0-100%
EEPR_TimeInit
EEPR - Time at Init Steps at the start time
1-200 Seconds
EEPR_del
EEPR - Delay before EEPR is 0% caused by system disable
0-3600 Seconds
EEPR_ExtraS_Cal
EEPR - Extra steps used for the first calibration after ExtraS_Cal_-
Time
1-2500 Steps
EEPR_LR
EEPR - Min Regulation Alarm Threshold (rel)
-40-90° relative to case temperature
setpoint
EEPR_MR
EEPR - Max Regulation Alarm Threshold (rel)
0-90° relative to case temperature
setpoint
EEPR_HSHd
EEPR - High Regulation Alarm Activation Delay
0-300 Seconds
EEPR_LSHd
EEPR - Low Regulation Alarm Activation Delay
0-300 Seconds
EEPR_PB
EEPR - Proportional Band (if 0, Regulation Auto Adaptive) of Regu-
lation
0-45°
EEPR_DB
EEPR - Dead Band of Regulation
-50-50°
EEPR_INC
EEPR - Integral of Regulation
0-255 Seconds
EEPR_DER
EEPR - Derivative of Regulation
0-255 Seconds
EEPR_ThrD
EEPR - Threshold of Integral decrease (rel)
-40-90°
EEPR_PercD
EEPR - Percentage of integral decrease below the threshold
0-100%
EEPR_ExtraCl
EEPR - Extra % of valve close in case of low alarm
0-500 Steps
EEPR_DutyCycle
EEPR - Valve Duty Cycle
100%
EEV 1-3 Valve Parameters
EEV1_MinS
EEV1 - Minimum Steps
0-50 where 1=10 Steps
EEV1_MaxS
EEV1 - Maximum Steps
0-800 where 1=10 Steps
EEV1_PeakC
EEV1 - Peak Current (Bipolar only)
0-100 where 1=10 mA
EEV1_HoldC
EEV1 - Hold Current (Bipolar only)
0-100 where 1=10 mA
EEV1_StepR
EEV1 - Step Rate
10-600 Steps
EEV1_ExtraS
EEV1 - Extra Steps
1-500 Steps
EEV1_RelaxS
EEV1 - Relax Steps
0-500 Steps
EEV1_PressF
EEV1 - Filter on the pressure
1-100 Seconds
EEV1_TempF
EEV1 - Filter on the temperature
1-100 Seconds
EEV1_InitS
EEV1 - Steps Init Regulation
Minimum of 2, maximum adjusts based
on MaxS. 1=10 Steps
EEV1_IntervU
EEV1 - Interval of updating
0-60 Seconds
EEV1_MaxP
EEV1 - Max Opening Percentage
0-100%
EEV1_MinP
EEV1 - Min Opening Percentage
0-100%
EEV1_TimeInit
EEV1 - Time at Init Steps at the start time
1-200 Seconds
EEV1_del
EEV1 - Delay before EEV1 is 0% caused by Enable DI
0-3600 Seconds
EEV1_ExtraS_Ca
EEV1 - Extra steps used for the first calibration after ExtraS_Cal_-
Time
1-2500 Steps
EEV1_LSH
EEV1 - Min Superheat Alarm Threshold
0-Setpoint
EEV1_MSH
EEV1 - Max Superheat Alarm Threshold
0-90°
Table 16-1