42
FXMP25 User Guide
www.controltechniques.com
Issue Number: 3
Indicates the last four field controller trips.
This parameter defines which parameter is displayed at power up. When the field
controller enters status mode this parameter is also displayed.
Used to define the unique address for the field controller for the serial interface. The
field controller is always a slave.
Addresses between 0 and 247 are permitted. Address 0 is used to globally address all
slaves, and so this address should not be set in this parameter.
Used to define the baud rate of the serial interface.
90
Trip 0
91
Trip 1
92
Trip 2
93
Trip 3
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
1
1
Range
0 to 255
Update rate
Background write
94
Parameter displayed at power-up
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
1
Range
00 to 98
Default
54
Update rate
Background read
95
Serial address
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
1
Range
0 to 247
Default
1
Update rate
Background read
96
Baud rate
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
1
1
Range
0 to 4
Default
3
Update rate
Background read
Parameter value
String/baud rate
0
2400
1
4800
2
9600
3
19200
4
38400