The programmable value of the armature back emf or armature voltage (standalone
mode), in volts, at which the field begins to weaken. Defined as the voltage at which
base speed is reached.
The calculated voltage being generated on the field output terminals. Calculated from
applied mains voltage and firing angle.
Gains used during field weakening. Setting these too high could cause instability during
field weakening.
Gains used during field weakening. Setting these too high could cause instability during
field weakening.
When this parameter is set to OFF (0) the field controller operates with the field
weakening voltage loop. When set to On (1) the flux level is determined by reference on
terminal 3.
59
Field weakening voltage set point
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
1
Range
0 to 750 V
Default
Eur: 400, USA: 480
Update rate
Background write
60
Field output voltage
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
Range
0 to 500 V
Update rate
Background write
62
Field weakening loop P gain
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
2
1
1
1
Range
0.00 to 99.99
Default
0.40
Update rate
Background read
63
Field weakening loop I gain
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
2
1
1
1
Range
0.00 to 99.99
Default
5.00
Update rate
Background read
64
External flux reference select
Coding
Bit
FI
Txt
VM
DP
ND
US
RW
BU
PS
1
1
Range
OFF (0) to On (1)
Default
OFF (0)
Update rate
Background read