Installation Operation & Maintenance manual ELQ
DOC.55.EDN Rev: E
October 2012
1
10
8
7
5
6
4
3
2
9
20
19
18
17
15
16
14
13
12
26
37
36
33
32
30
31
29
28
27
34
25
22
24
23
21
35
11
TX
24 V DC
+
-
5
CONNECtING CONtrOL SIGNALS
The ELQ-actuator has a terminal compartment with a
plug connector for control signals.
All control signals can be connected to the terminals
inside this compartment. In case of maintenance or
replacement of the valve/actuator unit, the terminal
compartment can be unplugged from the ELQ-actu
-
ator and plugged into an other actuator. You do not
need to reconnect all the control wiring.
Note
-
Before connecting the power supply connect
all options properly (see option instructions).
-
Use and mount cable glands as required by
national or local legislation.
-
When IP65, IP67 or NEMA4X ingress protec
-
tion is required, the electrical entries must be
fitted with equivalent or higher rated glands
or blindplugs.
AtEX Installation instructions
See chapter 1.2 and 1.3 for use of Flame
-
proof ELQ actuators in ATEX classified
hazardous areas.
Warning
Terminal compartment must be electronically
isolated before any disassembly is begun.
5.1
Connecting “Open” and “Close” con-
trol signals
A 24 V DC signal at 1 and 3 opens the actuator. A
signal at 2 and 3 closes the actuator.
No signal (or a signal at both), the actuator stops.
5.01 Terminal compartment
close
open
5.1.1 Connecting “Open” and “Close” control signals