The E2E’s standard I/O port (COM2, located on the E2E Power Interface Board, or PIB) also has two 

connectors (

Figure 1

). Unplug the connectors from the COM A and COM D plugs, and plug them into the 

COM2 plugs on the E2E.

STEP 3: E2E Termination Jumper Settings

The network termination jumpers, directly above the two COM2 plugs on the PIB, will need to be set to the 

same positions as the COM A and COM D termination jumpers on the RMCC/BEC/BCU. The rules for 

termination on E2E I/O networks are the same as the rules for RMCC/BEC/BCU I/O networks. Set the three 

jumpers to the middle 

I/O

 (terminated) position if the port is at the end of a network segment or the hub of 

a star configuration, and down 

NO

 (unterminated) if the port is in the middle of a segment.

There is one set of RS485 jumpers for each RS485 port (COM2A-2B; COM6; and COM4A-B). Jumpers J8-J10 

are located directly above the COM2A connector port, and jumpers J11-J13 are located directly above the 

COM2B port. The RS485 termination jumpers (J8-J22) are used to terminate the devices at the beginning 

and end of an RS485 Network. If the E2 is the beginning of all RS485 I/O or MODBUS Networks, all three of 

these jumpers should be set to the up position. For MODBUS, the jumpers should all be in the top-most 

position (

MOD

). For I/O Net, the jumpers should be in the middle position (

I/O

). For no termination, set the 

jumpers to the down position (

NO

). 

Refer to the E2E User’s Manual (

P/N 026-1614 Rev 5 or later)

 for expanded communication setup 

information. 

Содержание E2 Enhanced RX

Страница 1: ...RS232 COM C host network to connect all units to a modem for alarm dial out E2Es may use either Echelon or Ethernet for box to box communication The existing host network wiring may not be used for E2E box to box communication you will either have to rewire using approved Echelon network wire or wire CAT 5 cable to an approved network router or switch Refer to the E2E User s Guide for more informa...

Страница 2: ...CC BEC BCU I O networks Set the three jumpers to the middle I O terminated position if the port is at the end of a network segment or the hub of a star configuration and down NO unterminated if the port is in the middle of a segment There is one set of RS485 jumpers for each RS485 port COM2A 2B COM6 and COM4A B Jumpers J8 J10 are located directly above the COM2A connector port and jumpers J11 J13 ...

Страница 3: ... same baud rate all I O boards connected to the RMCC BEC BCU were also set to communicate at 19200 baud Because the default E2E baud rate for I O networks is 9600 baud you will need to change the COM2 baud rate setting This must be done in the C3 Serial tab of the E2E s General Controller Info screens 1 Log into the E2 with Level 4 password access 2 Press to access the General Controller Info scre...

Страница 4: ...collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 026 4157 19 FEB 2016 Emerson is a trademark of Emerson Electric Co ...

Отзывы: