![Emerson DIXELL XR30T Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/emerson/dixell-xr30t/dixell-xr30t_installing-and-operating-instructions_102159033.webp)
1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
33/40
odC=F-C
: compressor and evaporator fan OFF
When
rrd=Y
, the regulation restarts after
d1d
or
d2d
time.
11. CONDENSER FAN
To enable the condenser fan management, setting a condenser probe is required (par.
FAC
). Here are the
involved parameters:
FAC
: to select the control probe
St2
: to select the deactivation setpoint
HY2
: differential
FCC
: to define the working mode:
o
C-n:
in parallel with compressor output and stopped during any defrost. When compressor is OFF,
they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
O-n:
always ON, stopped during any defrost
o
C-Y:
in parallel with compressor output and always on during any defrost. When compressor is
OFF, they will start a duty-cycle mode (see
FoF
,
Fon
,
FF1
and
Fo1
parameters)
o
o-Y:
always on
12. DIGITAL OUTPUTS
Depending on the model, one or more digital outputs (relays) can be configurated with one of the following
functionalities.
12.1 COMPRESSOR OUTPUT (oAx = CP1)
With
oAx=CP1
the relay operates as the main regulation output.
12.2 DEFROST OUTPUT (oAx = dEF)
With
oAx=dEF
the relay operates as a defrost output.
12.3 EVAPORATOR FAN OUTPUT (oAx = FAn)
With
oAx=FAn
the relay operates as an evaporator fan output.
12.4 ALARM OUTPUT (oAx = ALr)
With
oAx=ALr
the output operates as an alarm output. It is activated every time an alarm happens. Its status
depends on the
tbA
parameter: if
tbA=Y
, the output is deactivated by pressing any key.
If
tbA=n
, the alarm output stays on until the alarm condition recovers.
12.5 LIGHT OUTPUT (oAx = LiG)
With
oAx=LiG
the relay operates as a light output.
12.6 AUXILIARY OUTPUT (oAx = AUS)
The auxiliary output can be managed by digital inputs (
oAx=AUS
,
i1F
or i2F=AUS
): the output is switched
on and off following the relative digital input status.
12.6.1 AUXILIARY REGULATOR
The auxiliary regulator can be used to manage the auxiliary output. Here are the involved parameters:
ACH:
type of regulation for the auxiliary relay:
Ht
= heating;
CL
=
cooling
SAA:
set point for auxiliary relay
SHY:
auxiliary relay differential
ArP:
probe for auxiliary relay
Sdd:
auxiliary output off during defrost
12.6.2 TIMED ACTIVATION
The following parameters can be used to define fixed activation and deactivation intervals.
btA:
base time for auxiliary output activation and deactivation intervals
Ato:
auxiliary activation interval
AtF:
auxiliary deactivation interval