Compressor ON time with faulty probe:
(0 to 255 min) time during which the compressor is active
in case of faulty thermostat probe. With
CY=0
compressor is always OFF.
CoF
Compressor OFF time with faulty probe:
(0 to 255 min) time during which the compressor is OFF
in case of faulty thermostat probe. With
Cn=0
compressor is always active.
5.1.2 Probe configuration parameters – Prb
P1C
Probe P1 selection:
(ntC; PtC; Pt1)
ntC
=NTC type;
PtC
=PTC type;
Pt1
=PT1000 type
P2C
Probe P2 selection:
(ntC; PtC; Pt1)
ntC
=NTC type;
PtC
=PTC type;
Pt1
=PT1000 type
P3C
Probe P3 selection:
(ntC; PtC; Pt1)
ntC
=NTC type;
PtC
=PTC type;
Pt1
=PT1000 type
P4C
Probe P4 selection:
(ntC; PtC; Pt1)
ntC
=NTC type;
PtC
=PTC type;
Pt1
=PT1000 type
ot
Probe P1 calibration:
(-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the first
probe.
P2P Probe P2 presence:
n
= not present;
Y
= present.
oE
Probe P2 calibration:
-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the
second probe.
P3P Probe P3 presence:
n
= not present;
Y
= the defrost present.
o3
Probe P3 calibration:
(-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the third
probe.
P4P Probe P4 presence:
n
= not present;
Y
= present.
o4
Probe P4 calibration:
(-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible offset of the forth
probe.
5.1.3 Visualization parameters - diS
CF
Temperature measurement unit:
(°C; °F)
°C
= Celsius;
°F
= Fahrenheit.
rES Temperature resolution:
(dE; in)
dE
= decimal;
in
= integer.
Lod
Probe default displayed:
(P1; P2; P3; P4; SEt; dtr; USr)
Px
=probe “x”;
SEt
=set point;
dtr
=do not
use it.
rEd
Remote probe displayed (for XH-REP):
(P1; P2; P3; P4; SEt; dtr; USr)
Px
=probe “x”;
SEt
=set
point;
dtr
=do not use it.
dLY
Temperature display delay:
(0.0 to 20min00sec, res. 10 sec) when the temperature increases, the
display is updated of 1°C or 1°F after this time.
dtr
Probe visualization percentage, F(P1; P2):
(0 to 100)
with
dtr=1
the display will show this value
VALUE=0.01*P1+0.99*P2
5.1.4 Defrost configuration parameters - dEF
EdF Defrost mode:
in
=fixed intervals;
rtC
=following real time clock
tdF
Defrost type: EL
=electrical heaters;
in
=hot gas;
dFP
Probe selection for defrost control:
(nP; P1; P2; P3; P4)
nP
=no probe;
Px
=probe “x”. Note:
P4
=Probe on Hot Key plug.
dtE
End defrost temperature:
(-55 to 50°C; -67 to 122°F) sets the temperature measured by the
evaporator probe (
dFP
), which causes the end of defrost cycle.
idF
Interval between two successive defrost cycles:
(0 to 255 hours) determines the time interval
between the beginning of two defrosting cycles.
MdF
Maximum length of defrost cycle:
(0 to 255 min; 0 means no defrost) when
P2P=n
(no
evaporator probe presence) it sets the defrost duration, when
P2P=Y
(defrost end based on
evaporator temperature) it sets the maximum length for the defrost cycle.
dSd Start defrost delay:
(0 to 255 min) delay in defrost activation.
StC
Compressor stop before starting any defrost:
(0 to 900 sec) interval with compressor OFF
before activating hot gas cycle
dFd
Display during defrost:
(rt; it; SP; dF)
rt
= real temperature;
it
= start defrost temperature;
SP
= SET-POINT;
dF
= label “
dF
”.
dAd
Temperature display delay after any defrost cycle:
(0 to 255 min) delay before updating the
temperature on the display after the end of any defrost.
Fdt
Draining time:
(0 to 255 min) regulation delay after finishing a defrost phase
Hon
Drain heater enabled after draining time (par. Fdt):
(0 to 255 min) the relative output will stay on
after draining time.
dPo Defrost cycle enebled at stat-up:
(n; Y) enables defrost at power on.
HYP Differential temperature during any pre-defrost phase:
(-12.0 to 12.0°C; -21 to 21°F)