1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
13/40
CoM
Serial Communication port configuration parameters
Ui
User Interface configuration parameters
inF
Information, read only parameters
PAS
Password for entering protected menu parameters
4.12 PASSWORD MENU
When in the
PAS
group, it is possible to set the password value by touching the
PRG
icon for 3 sec.
V-swipe on a single digit to modify the value, then confirm the password value by touching the
PRG
icon for
3 sec.
The new value will blink and after 2 sec the display will show:
Pr2
if the password is correct
Err
if the password value is wrong
After 2 sec the display will show the first group label (
rEG
) with a blinking
PRG
icon to indicate that protected
parameters now are editable.
5. PARAMETER TABLE
Here are the descriptions of the device parameters.
5.1
PARAMETER DESCRIPTION
5.1.1 Main regulation parameters - rEG
SEt Set Point:
range from LS to US
LS Minimum Set Point:
(-100.0°C to SET; -148°F to SET) fix the minimum value for the set point.
US Maximum Set Point:
(SET to 200.0°C; SET to 392°F) fix the maximum value for the set point.
HY
Compressor regulation differential in normal mode:
(0.1 to 25.0°C; 1 to 45°F) set point
differential. Compressor Cut-IN is
T > SET + HY
. Compressor Cut-OUT is
T<=SET
.
HYE
Compressor regulation differential in energy saving mode:
(0.1 to 25.0°C; 1 to 45°F) set point
differential. Compressor Cut-IN is
T > SET + HES + HYE
. Compressor Cut-OUT is
T<= SET + HES
.
odS
Output activation delay at start-up:
(0 to 255 min) this function is enabled after the instrument
power-on and delays the output activations.
AC
Anti-short cycle delay:
(0 to 50 min) minimum interval between a compressor stop and the
following restart.
rtr Regulation percentage=F(P1; P2) (100=P1; 0=P2):
100=P1 only; 0=P2 only
CCt
Maximum duration for Pull Down:
(0.0 to 23h50min, res. 10min) after elapsing this interval of time,
the super cooling function is immediately stopped
CCS
Pull Down phase differential (SET+CCS or SET+HES+CCS):
(-12.0 to 12.0°C; -21 to 21°F) during
any super cooling phase the regulation SETPOINT is moved to
SET+CCS
(in normal mode) or to
SET+HES+CCS
(in energy saving mode)
oHt
Threshold for automatic activation of Pull Down in normal mode (SET+HY+oHt):
(1.0 to 12.0°C;
1 to 21°F) this is the upper limit used to activate the super cooling function.
oHE
Threshold for automatic activation of Pull Down in energy saving mode
(SET+HES+HYE+oHE):
(1.0 to 12.0°C; 1 to 21°F) this is the upper limit used to activate the super
cooling function.