![Emerson DIXELL XR30T Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/emerson/dixell-xr30t/dixell-xr30t_installing-and-operating-instructions_102159026.webp)
1592040000 XR30-60-70T EN v1.3 2020.08.26
XR30-60-70T
26/40
5.3
PARAMETER CONFIGURATION 2
Group
Parameter Description
Value
Protected
U.O.M.
Range
rEG
SEt
Set Point
38.0
Pr1
°F
LS to US
rEG
LS
Minimum Set point
-148.0
Pr1
°F
[-100.0°C to SET]
[-148.0°F to SET]
rEG
US
Maximum Set point
302.0
Pr1
°F
[SET to 150.0°C]
[SET to 302.0°F]
rEG
HY
Compressor regulation differential in
normal mode
6.0
Pr1
°F
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
HYE
Compressor regulation differential in
energy saving mode
6.0
Pr1
°F
[0.1°C to 25.0°C]
[0.1°F to 45.0°F]
rEG
odS
Output activation delay at start-up
0
Pr1
min
0 to 255 min
rEG
AC
Anti-short cycle delay
0
Pr1
min
0 to 50 min
rEG
rtr
Regulation percentage=F(P1; P2)
(100=P1; 0=P2)
100
Pr2
0 to 100
rEG
CCt
Maximum duration for Pull Down
00:00
Pr2
hh:mm
0 to 23h50min
rEG
CCS
Pull Down phase differential (SET+CCS or
SET+HES+CCS)
0.0
Pr2
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
rEG
oHt
Threshold for automatic activation of Pull
Down in normal mode (SET+HY+oHt)
20.0
Pr2
°F
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
rEG
oHE
Threshold for automatic activation of Pull
Down in energy saving mode
(SET+HES+HYE+oHE)
20.0
Pr2
°F
[0.0°C to 25.0°C]
[0.0°F to 45.0°F]
rEG
Con
Compressor ON time with faulty probe
10
Pr1
min
0 to 255 min
rEG
CoF
Compressor OFF time with faulty probe
15
Pr1
min
0 to 255 min
Prb
P1C
Probe P1 selection
ntC
Pr2
ntC; PtC; Pt1
Prb
P2C
Probe P2 selection
ntC
Pr2
ntC; PtC; Pt1
Prb
P3C
Probe P3 selection
ntC
Pr2
ntC; PtC; Pt1
Prb
P4C
Probe P4 selection
ntC
Pr2
ntC; PtC; Pt1
Prb
ot
Probe P1 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
Prb
P2P
Probe P2 presence
Y
Pr1
n(0); Y(1)
Prb
oE
Probe P2 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
Prb
P3P
Probe P3 presence
no
Pr1
n(0); Y(1)
Prb
o3
Probe P3 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
Prb
P4P
Probe P4 presence
no
Pr1
n(0); Y(1)
Prb
o4
Probe P4 calibration
0
Pr1
°F
[-12.0°C to 12.0°C]
[-21.6°F to 21.6°F]
diS
CF
Temperature measurement unit: Celsius;
Fahrenheit
°F
Pr1
°C(0); °F(1)
diS
rES
Temperature resolution: decimal, integer
dE
Pr1
dE(0); in(1)
diS
Lod
Probe default displayed
P1
Pr1
P1(0); P2(1); P3(2);
P4(3); SEt(4); dtr(5)
diS
dLy
Temperature display delay (resolution 10
sec)
00:00
Pr1
mm:ss
0.0 to 20min00sec
diS
dtr
Probe visualization percentage=F(P1;P2)
(dtr=1 means VALUE=0.01*P1+0.99*P2)
99
Pr1
1 to 99
dEF
EdF
Defrost mode
rtC
Pr2
rtC(0); in(1)
dEF
tdF
Defrost type: electric heating, hot gas
EL
Pr2
EL(0); in(1)
dEF
dFP
Probe selection for defrost control
P2
Pr2
nP(0); P1(1); P2(2); P3(3); P4(4)
dEF
dtE
End defrost temperature
48.0
Pr2
°F
[-50.0°C to 50.0°C]
[-58.0°F to 122.0°F]
dEF
idF
Interval between two successive defrost
cycles
24
Pr2
ora
0 to 255 hours