1592026260 IEV22-24D GB r.1.0 21.02.2019 IEV 34/60
•
Ec17 / Ec26
=
maximum number of steps per second that can be carried out by the valve
(value to be calculated based on the technical documentation of the valve)
•
Ec50 / Ec52
=
type of movement or holding current: peak or RMS current. This is an
important value for the manual setting of the valve; some manufacturers declare the
maximum current values and still current values expressed as a peak value or an RMS value
(value to be calculated based on the technical documentation of the valve)
•
Ec51 / Ec53
=
type of current signal
;
this is an important value for the manual setting of the
valve. Some manufacturers use a microstepping or normal-mode control for their own valves
(value to be calculated based on the technical documentation of the valve)
•
Ec54
=
only reading parameter;
through this parameter it is possible to read how many
gases are selectable by Ec8 parameter
8.5
System configuration parameters
•
Ec4 / Ec5
= selection of the valves operating mode (cooling only / heating only / both)
•
Ec6 / Ec7
= selection of the cooling circuit of valve 1 and 2
•
Ec8
= type of gas used in the system (R134a, R407c,...)
8.6
Adjustment parameters
•
Et1 / Et4
= number of aperture steps at which the valve is set when the adjustment starts
and before turning on the compressor (if the IEV is used with a LAN connection to an IC200
EVO)
•
Et7 / Et27
= proportional contribution of the PID regulator in summer and winter mode.
If this parameter is set to 0, the Self-adaptive adjustment function is enabled.
Increasing the value means increasing the action Δt of the proportional part; therefore, upon
start-up of the deviation of the superheating calculated in relation to the setpoint value,
increasing the value means that the proportional part provides a smaller contribution to
adjustment.
•
Et8 / Et28
= integral time of the PID regulator in summer and winter adjustment mode.
Indicates the action time of the integral component; increasing the value means setting more
time to calculate the integral component.
•
Et9 / Et29
= derivative constant of the PID regulator in summer and winter adjustment mode.
•
Et10 / Et30
= superheating setpoint value in summer and winter mode
•
Et11 / Et31
= adjustment dead band. Within the dead band
Summer superheating setpoint
–
Et11 ÷ Summer superheating se Et11
in summer mode
Winter superheating setpoint
–
Et31 ÷ Winter superheating se Et31 in
winter mode
no action is taken in terms of adjustment. This will maintain the value calculated the moment
before entering the band
•
Et12 / Et32
= high superheating threshold
If the calculated superheating exceeds this value and remains above it for the Et49 time, the
regulator carried out corrections on the adjustment (in terms of valve aperture) in order to
reduce the superheating value and drop below this threshold again
•
Et13 / Et33
= low superheating threshold