Function
Range
Default
15D
Shorted SCR Action
3-Phase Control Only, PowerThrough
3-Phase Control Only
Selects whether the soft starter will allow PowerThrough operation. For critical applications this allows the soft starter to control the
motor with two-phase control, if the soft starter is damaged on one phase. PowerThrough only operates after the soft starter has
tripped on "Lx-Tx Shorted" and has been reset.
CAUTION
PowerThrough uses a two-phase soft start technology and additional care is required when sizing circuit breakers and
protection. Contact your local supplier for assistance.
PowerThrough remains active until '3-Phase Control Only' is reselected.
PowerThrough operation does not support Adaptive Control soft starting or soft stopping. In PowerThrough, the Digistart
IS will automatically select constant current soft starting and timed voltage ramp soft stopping. If PowerThrough is
enabled, Pr
2C
and
2B
must be set appropriately.
PowerThrough can only operate with internally bypassed soft starters.
NOTE
PowerThrough only operates with in-line connected motors.
No
Function
Range
Default
15E
Jog Torque
20 to 100%
50%
Sets the torque level for jog operation. See
Jog Operation
for details.
8.8.17 Group 16 - Protection action
These parameters define how the soft starter will respond to different protection events. The soft starter can trip, issue a warning, or
ignore different protection events as required. All protection events are written to the event log. The default action for all protections
is to trip the soft starter.
Protections
16P
Ground Fault
and
16R
to
16W
RTD/PT100
are only available if the RTD/PT100 and ground fault protection card
has been fitted.
CAUTION
Defeating the protection may compromise the starter and motor, and should only be done in the case of emergency.
No
Function
Range
Default
16A
Motor Overload
16B
Excess Start Time
16C
Current Imbalance
16D
Underpower
16E
Overpower
16F
Reserved
16G
Reserved
16H
Frequency
16I
Input A Trip
16J
Input B Trip
16K
Motor Thermistor
16L
Starter Communication
Trip Starter, Warn & Log, Log Only
Trip Starter
16M
Network Communication
16N
Heatsink Overtemperature
16O
Battery/Clock
16P
Ground Fault
16Q
RTD/PT100 A
16R
RTD/PT100 B
16S
RTD/PT100 C
16T
RTD/PT100 D
16U
RTD/PT100 E
16V
RTD/PT100 F
16W
RTD/PT100 G
16X
Low Control Volts
Selects the soft starter's response to each protection.