83
Issue: 4
www.controltechniques.com
Heat dissipation
During start ...................................................................................................................................................... 4.5 watts per ampere
During run
IS1x0023B to IS1x0053B .............................................................................................................................. ≤ 39 watts approx
IS1x0076B to IS1x0105B .............................................................................................................................. ≤ 51 watts approx
IS2x0145B to IS2x0220B ............................................................................................................................ ≤ 120 watts approx
IS3x0255B to IS4x0500B ............................................................................................................................ ≤ 140 watts approx
IS4x0700B to IS4x1000B ............................................................................................................................ ≤ 357 watts approx
IS3x0255N to IS4x0930N ............................................................................................................. 4.5 watts per ampere approx
IS561200N to IS561600N ............................................................................................................ 4.5 watts per ampere approx
Fan noise
IS1x0076B to IS2x0220B (excluding IS2x0170B) ...................................................................................................................... 32 db
IS3x0255B to IS4x1000B ........................................................................................................................................................... 49 db
IS3x0255N to IS4x0430N .......................................................................................................................................................... 49 db
IS4x0650N to IS4x0930N ......................................................................................................................................................... 56 db
IS561200N to IS561600N ........................................................................................................................................................ 58 db
Certification
UL/ C-UL ................................................................................................................................................................................ UL 508
IS1x0023B to IS1x0105B ....................................................................................................... IP20 & NEMA1, UL Indoor Type 1
IS2x0145B to IS4x1000B and IS3x0255N to IS561600N ................................................................. IP00, UL Indoor Open Type
CE .......................................................................................................................................................................... IEC 60947-4-2
CCC ............................................................................................................................................................................... GB 14048.6
C
......................................................................................................................................................................... IEC 60947-4-2
RoHS ................................................................................................................................. Compliant with EU Directive 2002/95/EC
Operational life (internal bypass contacts)
IS1x0023B to IS1x0105B ................................................................................................................................... 1,000,000 operations
IS2x0145B to IS4x1000B .................................................................................................................................... 100,000 operations
IS2x0220B to IS4x1000B: The contacts on the internal bypass contactors should be checked for wear after the stated
number of operations. Periodic servicing/replacements may be required.
* Contact your local supplier for advice.