10.6 Soft braking
For applications with high inertia and/or a variable load, the Digistart IS can be configured for soft braking.
In this application the Digistart IS is employed with forward run and braking contactors. When the Digistart IS receives a start signal
(pushbutton S1), it closes the forward run contactor (KM1) and controls the motor according to the programmed primary motor
settings.
When the Digistart IS receives a stop signal (pushbutton S2), it opens the forward run contactor (KM1) and closes the braking
contactor (KM2) after a delay of approximately 2-3 seconds (KT1). KA3 is also closed to activate the secondary motor settings,
which should be user programmed for the desired stopping performance characteristics.
When motor speed approaches zero, the zero speed detector (A2) stops the soft starter and opens the braking contactor (KM2).
Figure 10-6 Soft braking
1
Control voltage (model dependent)
KA3
Brake relay
2
Remote control inputs
KA4
Zero speed detector relay
3
Motor thermistor input
KM1
Line contactor (Run)
4
RTD/PT100 input
KM2
Line contactor (Brake)
5
Relay outputs
KT1
Run delay timer
6
Three-phase supply
KT2
Brake delay timer
7
Motor terminals
KT3
Zero speed detector delay timer*
A2
Zero speed detector
S1
Start contact
F1
Semiconductor fuses (optional)
S2
Stop contact
KA1
Run relay
S3
Reset contact
KA2
Start relay
* The KT3 timer is only required if the zero speed detector is the type that performs a self-test upon power-up and momentarily
closes the output relay.
Parameter settings:
Pr
3A
Input A Function
(terminals DI4, +24V)
Select 'Motor Set Select' - assigns Input A for Motor set selection.
Set starting performance characteristics using the primary motor set.
Set braking performance characteristics using the secondary motor settings.
Pr
4G
Relay C Function
Select 'Trip' - assigns Trip function to Relay Output C.
NOTE
If the Digistart IS trips on supply frequency (Pr
16H
Frequency
) when the braking contactor KM2 opens, modify the
frequency protection settings.
2
1
6
3
4
7
1
5
CSH
CSR
CSL
TH1
PT3
TH2
COM4
RLC4
DI3
DI1
DI2
DI4
+24V
08
53
7.
B
PT4 PT5
+24V
+24V
+24V
11
0-
21
0
VA
C
22
0-
44
0
VA
C