Digistart IS User Guide
www.controltechniques.com
Issue: 4
Parameter Group
Parameters
Default Value
13 - Slip-Ring Motors
M
13A
Motor Data-1 Ramp
Single Ramp
13B
Motor Data-2 Ramp
Single Ramp
13D
Slip Ring Retard
50%
13C
Changeover Time
150 ms
14 - RTD/PT100
M
14A
RTD/PT100 A °C
50 °C
14B
RTD/PT100 B °C
50 °C
14C
RTD/PT100 C °C
50 °C
14D
RTD/PT100 D °C
50 °C
14E
RTD/PT100 E °C
50 °C
14F
RTD/PT100 F °C
50 °C
14G
RTD/PT100 G °C
50 °C
15 - Restricted
M
15A
Access Code
0000
15B
Emergency Run
Disable
15C
Adjustment Lock
Read & Write
15D
Shorted SCR Action
3-Phase Control Only
15E
Jog Torque
50%
16 - Protection Action
M
16A
Motor Overload
Trip Starter
16B
Excess Start Time
Trip Starter
16C
Current Imbalance
Trip Starter
16D
Underpower
Trip Starter
16E
Overpower
Trip Starter
16F
Reserved
-
16G
Reserved
-
16H
Frequency
Trip Starter
16I
Input A Trip
Trip Starter
16J
Input B Trip
Trip Starter
16K
Motor Thermistor
Trip Starter
16L
Starter Communication
Trip Starter
16M
Network Communication
Trip Starter
16N
Heatsink Overtemperature
Trip Starter
16O
Battery/Clock
Trip Starter
16P
Ground Fault
Trip Starter
16Q
RTD/PT100 A
Trip Starter
16R
RTD/PT100 B
Trip Starter
16S
RTD/PT100 C
Trip Starter
16T
RTD/PT100 D
Trip Starter
16U
RTD/PT100 E
Trip Starter
16V
RTD/PT100 F
Trip Starter
16W
RTD/PT100 G
Trip Starter
16X
Low Control Volts
Trip Starter