Quick Installation Guide
Test of DPI-E, On/Off signals
IG 8000-81-003 Ed 01
February 2020
16
5.
Set the multimeter to
sound signals.
6.
Test of ‘Closed’ signal:
The multimeter should
give a sound signal when
connecting the multime-
ter to terminal 9 + 10.
7.
Operate the hand pump
until the actuator is fully
‘Open’ (spindle moves in).
The sound signal should
turn off.
8.
Test of ‘Open’ signal:
The multimeter should
give a sound signal when
connecting the multime-
ter to terminal 7 + 8.
Caution!
If any of the sound signals described above fail to appear, please consult the description for
adjustment of the DPI on page 19.
9.
Disconnect the multimeter.
10.
Leave the actuator in position 'Closed' = actuator spindle is max. out.
Содержание Damcos KC 125
Страница 4: ...Quick Installation Guide Table of Contents RM 8000 100 01 Ed 01 February 2020 2 ...
Страница 6: ...Quick Installation Guide General Information QIG 8000 81 003 Ed 01 February 2020 4 ...
Страница 7: ...Quick Installation Guide February 2020 QIG 8000 81 003 Ed 01 5 Normal Installation ...
Страница 8: ...Quick Installation Guide QIG 8000 81 003 Ed 01 February 2020 6 ...
Страница 24: ...Quick Installation Guide Damcos KC Actuators Adjustment of the DPI QIG 8000 81 003 Ed 01 February 2020 22 ...
Страница 26: ...Quick Installation Guide Determine the Configured Stroke QIG 8000 81 003 Ed 01 February 2020 24 ...
Страница 28: ...Quick Installation Guide Trouble Shooting QIG 8000 81 003 Ed 01 February 2020 26 ...
Страница 30: ...Quick Installation Guide QIG 8000 81 003 Ed 01 February 2020 28 ...
Страница 40: ...Quick Installation Guide QIG 8000 81 003 Ed 01 February 2020 38 ...
Страница 41: ...Quick Installation Guide February 2020 QIG 8000 81 003 Ed 01 39 Appendix A ...
Страница 42: ...Quick Installation Guide QIG 8000 81 003 Ed 01 February 2020 40 ...
Страница 45: ......