The pumpdown function of the CO

2

 refrigeration unit does not work in the same way as in units using standard 

refrigerants.  Based  on  the  ambient  temperature  and  the  compressor  setpoint,  the  controller  calculates  two 
different pumpdown setpoints: 

  Setpoint based on ambient temperature = T

Amb

 

– SPF5 

  Setpoint based on compressor setpoint = SETC1 

– SPF1 

The lowest pumpdown setpoint will always be applied. The following diagram illustrates the controller logic: 

 

Figure 8: Controller logic for the pumpdown function 

NOTE: The pumpdown setpoint will never be lower than what parameter RC02 allows. 

-18°C < 0°C 

Controller will perform 

pumpdown down to 

-18°C

 

Ambient condition: 

T

Amb

 = 20°C 

SPF5 = 20K 

Compressor setpoint: 

SETC1 = -10°C 

SPF1 = 8K 

Pumpdown setpoint based 

on ambient temperature: 

T

Amb

 

– SPF5 = 0°C

 

Pumpdown setpoint based on 

compressor setpoint: 

SETC1 

– SPF1

 

= -18°C

 

Содержание Copeland EazyCool CO2

Страница 1: ...sure side piping has been finalized and the electrical supply has been connected by qualified personnel please follow the steps below in preparation for commissioning Safety Verification of necessary safety devices in the system Visual inspection of the refrigerant pipes and especially of all connections Visual inspection of the electrical wiring of the supply line Checking the refrigeration unit ...

Страница 2: ...to be opened closed in order to carry out the pressure tests For the evacuation process it is recommended that all shut off devices be opened and evacuated from both sides via the connections on the suction side and the connection on the liquid receiver The shut off valves at the discharge port on the suction side of the compressor at the outlet of the liquid receiver and the shut off valve in the...

Страница 3: ...his serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump IMPORTANT Care must be taken that all components solenoids expansion devices regulators shut off valves etc in the refrigeration cycle which separate a part of the installation when de energized are manually opened to guarantee successful evacuation in the whole piping system NOTE...

Страница 4: ...ity over the valves override function 2 The compressor is switched off safety timers are ignored 3 The fan is switched off while auxiliary outputs are not influenced safety timers are ignored 4 The alarms are disabled except for the communication alarms Stopping the evacuation function The evacuation mode will be deactivated when 1 One of the 3 pressures probes P1 P2 P3 SPF6 or 2 the DISB key is p...

Страница 5: ...ressors F1 and fans F3 must be switched on and the release for the frequency inverter SB1 must be activated Figure 7 Enabling compressors fans frequency inverter The refrigeration unit starts automatically First the gas cooler fans start up then the compressor switches on and starts controlling according to suction pressure The filling process via the suction side can be completed The system shoul...

Страница 6: ... OFF 8 Use the UP and DOWN keys to adjust GC78 to the desired value 9 Press SET to apply the setting 10 Press EXIT to leave the menu GC20 Medium pressure flashtank setpoint Setpoint for the pressure in the liquid receiver in normal control mode GC78 Bypass medium pressure vessel Pressure with compressor OFF Maximum pressure in the liquid receiver during standstill of the refrigeration unit When th...

Страница 7: ...on compressor setpoint SETC1 SPF1 The lowest pumpdown setpoint will always be applied The following diagram illustrates the controller logic Figure 8 Controller logic for the pumpdown function NOTE The pumpdown setpoint will never be lower than what parameter RC02 allows 18 C 0 C Controller will perform pumpdown down to 18 C Ambient condition TAmb 20 C SPF5 20K Compressor setpoint SETC1 10 C SPF1 ...

Отзывы: