CC7.8.9/0519/E 

 

5/7

 

Charging the CO

2

 refrigeration unit 

 

CAUTION 
High pressures! Risk of system damage!

 Only use pressure gauges that are suitable 

for the required pressure positions. Check the connection hoses for suitability for CO

2

 

pressure levels. 

 

After leakage tests and evacuation have been performed, the system can be filled with R744 refrigerant. In 
order to avoid the formation of dry ice, the system must be filled with gas on both sides first. Gaseous filling to 
10 bar is common practice. 

NOTE:  Only  pressure  gauges  and  connection  hoses  suitable  for  high-pressure  refrigerants  can  be 
used. 

 

Figure 6: Pressure gauges and connection hoses 

After  filling  to  approximately  10  bar  on  both  sides,  liquid  CO

2

  can  be  filled  into  the  liquid  receiver.  After 

pressures in the refrigeration system and the CO

2

 tank have equalised, the missing refrigerant must be refilled 

in gaseous form via the suction side. 

For  this  purpose,  the  isolating  switches  for  compressors  (

F1

)  and  fans  (

F3

)  must  be  switched  on  and  the 

release for the frequency inverter (

SB1

) must be activated. 

 

Figure 7: Enabling compressors, fans & frequency inverter 

The refrigeration unit starts automatically. First the gas cooler fans start up, then the compressor switches on 
and starts controlling according to suction pressure. The filling process via the suction side can be completed. 

The system should be charged according to the liquid level in the bottom sight glass on the liquid receiver. As 
soon as the bottom sight glass is completely charged with liquid CO

2

, a sufficient refrigerant charge is available. 

The influence of the ambient temperature is negligible, as the pressure in the liquid receiver is regulated and 
therefore the temperature in the receiver is constant. At low pressure in the refrigerant bottle, the evaporation 
pressure "

SETC1

" can be set low to enable filling from the suction side. 

During normal operation, the upper sight glass should not contain liquid refrigerant. Refrigerant in the upper 
sight glass would be an indication of system overfilling. During pumpdown however, refrigerant may be present 
in the upper sight glass. 

 

 

Содержание Copeland EazyCool CO2

Страница 1: ...sure side piping has been finalized and the electrical supply has been connected by qualified personnel please follow the steps below in preparation for commissioning Safety Verification of necessary safety devices in the system Visual inspection of the refrigerant pipes and especially of all connections Visual inspection of the electrical wiring of the supply line Checking the refrigeration unit ...

Страница 2: ...to be opened closed in order to carry out the pressure tests For the evacuation process it is recommended that all shut off devices be opened and evacuated from both sides via the connections on the suction side and the connection on the liquid receiver The shut off valves at the discharge port on the suction side of the compressor at the outlet of the liquid receiver and the shut off valve in the...

Страница 3: ...his serves to avoid incorrect measurements resulting from the pressure gradient along the connecting lines to the pump IMPORTANT Care must be taken that all components solenoids expansion devices regulators shut off valves etc in the refrigeration cycle which separate a part of the installation when de energized are manually opened to guarantee successful evacuation in the whole piping system NOTE...

Страница 4: ...ity over the valves override function 2 The compressor is switched off safety timers are ignored 3 The fan is switched off while auxiliary outputs are not influenced safety timers are ignored 4 The alarms are disabled except for the communication alarms Stopping the evacuation function The evacuation mode will be deactivated when 1 One of the 3 pressures probes P1 P2 P3 SPF6 or 2 the DISB key is p...

Страница 5: ...ressors F1 and fans F3 must be switched on and the release for the frequency inverter SB1 must be activated Figure 7 Enabling compressors fans frequency inverter The refrigeration unit starts automatically First the gas cooler fans start up then the compressor switches on and starts controlling according to suction pressure The filling process via the suction side can be completed The system shoul...

Страница 6: ... OFF 8 Use the UP and DOWN keys to adjust GC78 to the desired value 9 Press SET to apply the setting 10 Press EXIT to leave the menu GC20 Medium pressure flashtank setpoint Setpoint for the pressure in the liquid receiver in normal control mode GC78 Bypass medium pressure vessel Pressure with compressor OFF Maximum pressure in the liquid receiver during standstill of the refrigeration unit When th...

Страница 7: ...on compressor setpoint SETC1 SPF1 The lowest pumpdown setpoint will always be applied The following diagram illustrates the controller logic Figure 8 Controller logic for the pumpdown function NOTE The pumpdown setpoint will never be lower than what parameter RC02 allows 18 C 0 C Controller will perform pumpdown down to 18 C Ambient condition TAmb 20 C SPF5 20K Compressor setpoint SETC1 10 C SPF1 ...

Отзывы: