Nailor AT303 Скачать руководство пользователя страница 1

  SCHEDULE TYPE:
 PROJECT:
 ENGINEER:
 CONTRACTOR:

Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.

 

DATE 

B SERIES 

SUPERSEDES   DRAWING NO.

  3 - 30 - 17 

3000 

3 - 21 - 13 

30AT

Dimensions are in inches (mm)

SINGLE DUCT TERMINAL UNIT

ACCESSORY • DISCHARGE SOUND ATTENUATOR

MODELS: AT303 AND AT305

Accessories:

Accessories ordered as seperate models.

Options:

q

 Steri-Liner.

q

 Fiber-Free Liner.

q

 Solid Metal Liner.

q

 1" (25) Fiberglass Liner.

q

 2" (51) Fiberglass Liner.

q

 Perforated Metal Liner.

q

 Steri-Liner with Perforated Liner.

q

 Access Door

  Sizes 4 to 12 : 8" x 5" (203 x 127) Oval; 

Sizes 14 to 24 x 16: 12" x 6" (305 x 152) Oval.

q

 Special Features: _____________.

Note: Select Insulation to match VAV terminal.

Dimensional Data

Unit 

Size

W

H

AD

4, 5, 6

10 (254)

10 (254)

12 (305)

7, 8

12 (305)

12 1/2 (318)

12 (305)

9, 10

14 (356)

12 1/2 (318)

12 (305)

12

18 (457)

12 1/2 (318)

12 (305)

14

24 (610)

12 1/2 (318)

12 (305)

16

28 (711)

12 1/2 (318)

12 (305)

24 x 16

38 (965)

18 (457)

12 (305)

H

L = 36" (914) OR 59" (1499)

AD

W

SIDE VIEW

END VIEW

OPTIONAL ACCESS DOOR

AT Discharge Sound Attenuator (loose)

• 22 ga. (0.86) galvanized steel 

construction.
• 

Shipped loose for field 

attachment.
• Slip and drive connection.
• 3/4" (14) dual density fiberglass 

insulation, exposed edges 

coated to prevent erosion as 

standard. 

q

 

AT303

 3´ (916) Long - 

Standard.

q

 

AT305

 5´ (1524) Long - 

Optional.

q

 Special Features:

  ____________________ .

Содержание AT303

Страница 1: ...to 12 8 x 5 203 x 127 Oval Sizes 14 to 24 x 16 12 x 6 305 x 152 Oval q Special Features _____________ Note Select Insulation to match VAV terminal Dimensional Data Unit Size W H AD 4 5 6 10 254 10 254 12 305 7 8 12 305 12 1 2 318 12 305 9 10 14 356 12 1 2 318 12 305 12 18 457 12 1 2 318 12 305 14 24 610 12 1 2 318 12 305 16 28 711 12 1 2 318 12 305 24 x 16 38 965 18 457 12 305 H L 36 914 OR 59 149...

Страница 2: ...et size to be specified per M O A No mixing of outlet sizes on the same unit Number and size of outlets on M O A not to exceed the limits listed in table both maximum quantity of outlets and maximum size of outlet All round outlets c w manual dampers with hand locking quadrant Denotes inlet air flow direction For special outlet sizes and arrangements consult your Nailor representative Options q St...

Страница 3: ...gle Operation is not affected by position Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories q Steri liner q Fiber free liner q Solid metal liner q Perforated Metal Liner q 1 25 liner q Bottom access door q 24 VAC control transformer q Toggle disconnect switch q Hanger brackets q Controls enclosure for field mounted controls q Dust...

Страница 4: ... AT303 3 916 Long Standard q AT305 5 1524 Long Optional q Special Features ____________________ Dimensional Data Unit Size W H AD FF Nominal Outlet Size 4 5 6 10 254 10 254 12 305 4 5 6 102 127 152 7 8 12 305 12 1 2 318 12 305 7 8 178 203 9 10 14 356 12 1 2 318 12 305 9 10 229 254 12 18 457 12 1 2 318 12 305 12 305 14 24 610 12 1 2 318 12 305 14 356 16 28 711 12 1 2 318 12 305 16 406 24 X 16 38 96...

Страница 5: ...coustic media Internal insulation on top and bottom exposed panels optimizes sound reduction and eliminates need for external field applied thermal duct wrap Digital Controls q Nailor EZvav See separate submittal q Factory mount by others q Field mount Options and Accessories q 24 VAC control transformer q Bottom access door q Controls enclosure for field mounted controls q Dust tight enclosure se...

Страница 6: ...5 Round 10 0 1840 0 868 14 356 12 1 2 318 9 7 8 251 Round 12 0 2500 0 1180 18 457 12 1 2 318 12 15 16 x 9 13 16 329 x 249 Oval 14 0 3125 0 1475 24 610 12 1 2 318 16 1 16 x 9 13 16 408 x 249 Oval 16 0 3725 0 1758 28 711 12 1 2 318 19 3 16 x 9 13 16 487 x 249 Oval 24 x 16 0 8330 0 3931 38 965 18 457 23 7 8 x 15 7 8 606 x 403 Rect Dimensional Data Bottom mount controls location with vertical drive sh...

Страница 7: ...ication and full seam length steel Z strip construction Right hand controls location is standard shown when looking in direction of airflow Optional left hand controls mounting is available Silencer Section Designed to mate with VAV section for optimum performance and super quiet operation Optimized internal baffle geometry reduces self generated noise minimizes pressure drop and maximizes acousti...

Страница 8: ... internal baffle geometry reduces self generated noise minimizes pressure drop and maximizes acoustic attenuation 22 ga 0 86 coated steel perforated baffles encapsulate fiberglass acoustic media Mylar lining with acoustical spacer isolates material from airstream Internal Steri Liner insulation on top and bottom optimizes sound reduction and eliminates need for externally field applied thermal duc...

Страница 9: ...e when heating from the ceiling Never select kW to exceed a discharge temperatures of 120 F 49 C ΔT Air Temp Rise F kW x 3160 cfm The coils ranges listed are restricted to a maximum of 48 amps and do not require circuit fusing to meet NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping...

Страница 10: ...metry reduces self generated noise minimizes pressure drop and maximizes acoustic attenuation 22 ga 0 86 coated steel perforated baffles encapsulate fiberglass acoustic media Mylar lining with acoustical spacer isolates material from airstream Internal Steri Liner insulation on top and bottom optimizes sound reduction and eliminates need for external field applied thermal duct wrap Hot Water Coil ...

Страница 11: ...r q Fiber free liner q Solid metal liner q Perforated Metal Liner q 1 25 liner q Bottom access door q Hanger brackets q Controls enclosure for field mounted controls q Dust tight enclosure seal q 20 ga 1 00 construction Seismic Certification q SSI Standard q OSHPD q Special Features ______________ Electric Coil Features Options and Accessories See page 2 of 2 Maximum airflow limit is based upon 1 ...

Страница 12: ...Temp Rise F kW x 3160 cfm The coils ranges listed are restricted to a maximum of 48 amps and do not require circuit fusing to meet NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping of the thermal cutouts due to insufficient airflow a minimum airflow of 70 cfm 33 l s per kilowatt must...

Страница 13: ...n when looking in direction of airflow Optional left hand controls mounting is available Silencer Section Designed to mate w VAV section for optimum performance and super quiet operation Optimized internal baffle geometry reduces self generated noise minimizes pressure drop and maximizes acoustic attenuation 22 ga 0 86 coated steel perforated baffles encapsulate fiberglass acoustic media Internal ...

Страница 14: ...ceiling Never select kW to exceed a discharge temperatures of 120 F 49 C ΔT Air Temp Rise F kW x 3160 cfm The coils ranges listed are restricted to a maximum of 48 amps and do not require circuit fusing to meet NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping of the thermal cutouts ...

Страница 15: ... Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories q Steri liner q Fiber free liner q Soli...

Страница 16: ...l Dimensional Data Unit Size W H AD Hot Water Coil FF Nominal Outlet Size L 1 2 row L 3 4 row 4 5 6 10 254 10 254 12 305 5 127 7 1 2 191 4 5 6 102 127 152 7 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 7 8 178 203 9 10 14 356 12 1 2 318 12 305 5 127 7 1 2 191 9 10 229 254 12 18 457 12 1 2 318 12 305 5 127 7 1 2 191 12 305 14 24 610 12 1 2 318 12 305 5 127 7 1 2 191 14 356 16 28 711 12 1 2 318 12 305...

Страница 17: ...13 Copper tubes and aluminum ripple fins 10 per inch 20 ga 1 00 zinc coated steel casing Uninsulated Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Digital Controls q Nailor EZvav q Factory mount by others q Field mount See separate submittal 5 1 2 140 H DAMPER DRIVESHAFT L SLIP AND DRIVE CONNEC...

Страница 18: ...Q Options and Accessories q 24 VAC control transformer q Bottom access door q Controls enclosure for field mounted controls q Dust tight enclosure seal q FMI Removable insert type Diamond Flow Sensor q Hanger brackets q Toggle disconnect switch Seismic Certification q SSI Standard q OSHPD q Special Features ______________ Terminal Unit Liner q Fiber free liner q Perforated liner q Solid metal line...

Страница 19: ... external field applied thermal duct wrap Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 20 ga 1 00 zinc coated steel casing Uninsulated Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Digital Controls q Nailor EZvav q Factory mount by others q Field mount See sep...

Страница 20: ...ITH BOTTOM MOUNT CONTROLS LOCATION OPTION OB Options and Accessories q 24 VAC control transformer q Bottom access door q Controls enclosure for field mounted controls q Dust tight enclosure seal q FMI Removable insert type Diamond Flow Sensor q Hanger brackets q Toggle disconnect switch q Special Features ______________ Terminal Unit Liner q Fiber free liner q Perforated liner q Solid metal liner ...

Страница 21: ...n when looking in direction of airflow Optional left hand controls mounting is available Model D3101 can be installed horizontally vertical or at any angle Operation is not affected by position Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories q Steri liner q Fiber free liner q Solid metal liner q 1 25 liner q Bottom access door q...

Страница 22: ...ulation reduces insulation seams and minimizes airflow disturbance Supplied with same liner as basic unit q Integral Sound Attenuator Dimensional Data Unit Size W H FF Nominal Outlet Size 4 5 6 12 305 8 203 4 5 6 102 127 152 7 8 12 305 10 254 7 8 178 203 9 10 14 356 12 1 2 318 9 10 229 254 12 16 406 15 381 12 305 14 20 508 17 1 2 445 14 356 16 24 610 18 457 16 406 24 x 16 38 965 18 457 H 36 914 ST...

Страница 23: ...n Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories Maximum airflow limit is based upon 1 5 w g 373 Pa max differential pressure signal from Diamond Flow Sensor Unit Size Airflow Range cfm l s W H Inlet Size D C...

Страница 24: ...ow disturbance q Integral Sound Attenuator plus Hot Water Coil Unit Size W H Hot Water Coil FF Nominal Outlet Size L 1 2 Row L 3 4 Row 4 5 6 12 305 8 203 5 127 7 1 2 191 4 5 6 102 127 152 7 8 12 305 10 254 5 127 7 1 2 191 7 8 178 203 9 10 14 356 12 1 2 318 5 127 7 1 2 191 9 10 229 254 12 16 406 15 381 5 127 7 1 2 191 12 305 14 20 508 17 1 2 445 5 127 7 1 2 191 14 356 16 24 610 18 457 5 127 7 1 2 1...

Страница 25: ...losure for factory mounted controls 3 4 19 dual density insulation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Right hand controls location is standard shown when looking in direction of airflow Optional left hand controls mounting is available Controls K Digital by others K Analog by Nailor See separate submittal Options and Accessories K Steri liner ...

Страница 26: ...ion minimizes casing leakage Continuous internal insulation reduces insulation seams and minimizes airflow disturbance Supplied with same liner as basic unit Integral Sound Attenuator FF Round Discharge Collar 4 102 H END VIEW NOM 1 8 3 2 51 W SIDE VIEW AT Discharge Sound Attenuator loose Shipped loose for field attachment Slip and drive connection Supplied as standard with same liner as basic uni...

Страница 27: ...8 457 19 3 16 x 9 13 16 487 x 249 Oval 23 7 8 x 15 7 8 606 x 403 Rect Standard Features 22 ga 0 86 zinc coated steel casing mechanically sealed low leakage construction 16 ga 1 63 corrosion resistant steel inclined opposed blade damper with extruded PVC seals single blade on size 4 5 6 45 rotation CW to close Tight close off Damper leakage is less than 2 of the terminal rated airflow at 3 w g 750 ...

Страница 28: ...03 9 10 14 356 12 1 2 318 9 10 229 254 12 18 457 12 1 2 318 12 305 14 24 610 12 1 2 318 14 356 16 28 711 12 1 2 318 16 406 24 x 16 38 965 18 457 4 102 H END VIEW NOM 1 8 3 2 51 W SIDE VIEW H L 36 914 OR 59 1499 AD W SIDE VIEW END VIEW OPTIONAL ACCESS DOOR q FF Round Discharge Collar q AT Discharge Sound Attenuator loose 22 ga 0 86 galvanized steel construction Shipped loose for field attachment Sl...

Страница 29: ...lation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Electric Coil is mounted in an integral attenuator section Right hand controls location is standard shown when looking in direction of airflow Optional left hand controls mounting is available Controls q By Nailor See separate submittal q By others Unit Options and Accessories q Steri liner q Fiber fre...

Страница 30: ...160 cfm The coils ranges listed are restricted to a maximum of 48 amps and do not require circuit fusing to meet NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping of the thermal cutouts due to insufficient airflow a minimum airflow of 70 cfm 33 l s per kilowatt must be maintained Che...

Страница 31: ...ng is available Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q By Nailor See separate submittal q By others Options and Accessories q Steri liner q Fiber free liner q Solid metal liner q 1 2...

Страница 32: ...onal Data Unit Size W H AD Hot Water Coil FF Nominal Outlet Size L 1 2 row L 3 4 row 4 5 6 10 254 10 254 12 305 5 127 7 1 2 191 4 5 6 102 127 152 7 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 7 8 178 203 9 10 14 356 12 1 2 318 12 305 5 127 7 1 2 191 9 10 229 254 12 18 457 12 1 2 318 12 305 5 127 7 1 2 191 12 305 14 24 610 12 1 2 318 12 305 5 127 7 1 2 191 14 356 16 28 711 12 1 2 318 12 305 5 127 7 ...

Страница 33: ...nt averaging Diamond Flow Sensor Aluminum construction Supplied with balancing tees Rectangular discharge with slip and drive cleat duct connection Full NEMA 1 type controls enclosure for factory mounted controls 3 4 19 dual density insulation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Controls q Digital by others q Analog by Nailor See separate submi...

Страница 34: ...Supplied with same liner as basic unit q Integral Sound Attenuator Dimensional Data Unit Size W H AD FF Outlet Size 4 5 6 10 254 10 254 12 305 4 5 6 102 127 152 7 8 12 305 12 1 2 318 12 305 7 8 178 203 9 10 14 356 12 1 2 318 12 305 9 10 229 254 12 18 457 12 1 2 318 12 305 12 305 14 24 610 12 1 2 318 12 305 14 356 16 28 711 12 1 2 318 12 305 16 406 24 x 16 38 965 18 457 12 305 4 102 H END VIEW NOM ...

Страница 35: ...formance and super quiet operation Optimized internal baffle geometry reduces self generated noise minimizes pressure drop and maximizes acoustic attenuation 22 ga 0 86 coated steel perforated baffles encapsulate fiberglass acoustic media Mylar lining with acoustical spacer isolates material from airstream Internal Steri Liner insulation on top and bottom optimizes sound reduction and eliminates n...

Страница 36: ...V30HWC124 5 127 4 3 4 121 9 16 14 1 3 16 30 7 8 22 V30HWC224 5 127 4 3 4 121 7 8 22 7 8 22 7 8 22 Unit Size W H 3 Row 4 Row Part No L A B C D Part No L A B C D 4 5 6 10 254 10 254 V30HWC306 7 1 2 191 4 1 4 108 23 32 18 23 32 18 7 8 22 V30HWC406 7 1 2 191 4 1 4 108 11 16 17 11 16 17 7 8 22 7 8 12 305 12 1 2 318 V30HWC308 7 1 2 191 4 1 4 108 23 32 18 23 32 18 7 8 22 V30HWC408 7 1 2 191 4 1 4 108 11 ...

Страница 37: ...18 457 V30HWC124H 5 127 4 3 4 121 9 16 14 1 3 16 30 7 8 22 V30HWC224H 5 127 4 3 4 121 7 8 22 7 8 22 7 8 22 Unit Size W H 3 Row 4 Row Part No L A B C D Part No L A B C D 4 5 6 10 254 10 254 V30HWC306H 7 1 2 191 4 1 4 108 23 32 18 23 32 18 7 8 22 V30HWC406H 7 1 2 191 4 1 4 108 11 16 17 11 16 17 7 8 22 7 8 12 305 12 1 2 318 V30HWC308H 7 1 2 191 4 1 4 108 23 32 18 23 32 18 7 8 22 V30HWC408H 7 1 2 191 ...

Страница 38: ...tal liner q 1 25 liner q Side access door q 24 VAC Control transformer q Hanger brackets q Controls enclosure for field mounted controls q Dust tight enclosure seal q 20 ga 1 00 construction q Special Features _____________________ Electric Coil Features Options and Accessories See page 2 of 2 Minimum flows are based upon 0 02 w g differential pressure from flow sensor The maximum flow rate repres...

Страница 39: ...48 amps and do not require circuit fusing to meet NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping of the thermal cutouts due to insufficient airflow a minimum airflow of 70 cfm 33 l s per kilowatt must be maintained Check that desired minimum airflow is within recommended operating...

Страница 40: ...q Special Features ___________________________ DATE B SERIES SUPERSEDES DRAWING NO 3 30 17 3000 8 3 09 D30RW 2 Page 1 of 2 Dimensions are in inches mm SINGLE DUCT TERMINAL UNIT W HOT WATER REHEAT DIGITAL OR ANALOG CONTROLS CONSTANT OR VARIABLE VOLUME PRESSURE INDEPENDENT MODELS D30RW AND A30RW WITH BOTTOM MOUNT CONTROLS LOCATION OPTION OB OPTIONAL ACCESS DOOR SLIP AND DRIVE CONNECTION 14 356 5 1 2...

Страница 41: ...tenuator plus Hot Water Coil Dimensional Data Unit Size W H AD Hot Water Coil FF Outlet Size L 1 2 row L 3 4 row 4 5 6 10 254 10 254 12 305 5 127 7 1 2 191 4 5 6 102 127 152 7 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 7 8 178 203 9 10 14 356 12 1 2 318 12 305 5 127 7 1 2 191 9 10 229 254 12 18 457 12 1 2 318 12 305 5 127 7 1 2 191 12 305 14 24 610 12 1 2 318 12 305 5 127 7 1 2 191 14 356 16 28 71...

Страница 42: ...ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories q Steri liner q Fiber free liner q Solid metal liner q 1 25 liner q Hanger brackets q Bottom...

Страница 43: ...s basic unit q Integral Sound Attenuator plus Hot Water Coil Dimensional Data Unit Size W H AD Hot Water Coil FF Nominal Outlet Size L 1 2 row L 3 4 row 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 8 203 10 14 356 12 1 2 318 12 305 5 127 7 1 2 191 10 254 12 18 457 12 1 2 318 12 305 5 127 7 1 2 191 12 305 14 24 610 12 1 2 318 12 305 5 127 7 1 2 191 14 356 16 28 711 12 1 2 318 12 305 5 127 7 1 2 191 1...

Страница 44: ...NG NO 3 15 18 3000 2 19 18 D30RW OC 2 Page 1 of 2 Dimensions are in inches mm SINGLE DUCT TERMINAL UNIT W HOT WATER REHEAT OVERSIZED CASING LARGER WATER COIL DIGITAL OR ANALOG CONTROLS CONSTANT OR VARIABLE VOLUME PRESSURE INDEPENDENT MODELS D30RW AND A30RW WITH BOTTOM MOUNT CONTROLS LOCATION OPTION OB OPTIONAL ACCESS DOOR SLIP AND DRIVE CONNECTION 14 356 5 1 2 140 6 152 1 2 13 INLET ROUND OR FLAT ...

Страница 45: ...upplied with same liner as basic unit q Integral Sound Attenuator plus Hot Water Coil Dimensional Data 4 102 H END VIEW NOM 1 8 3 2 51 W SIDE VIEW H L 36 914 OR 59 1499 AD W SIDE VIEW END VIEW OPTIONAL ACCESS DOOR q FF Round Discharge Collar q AT Discharge Sound Attenuator loose 22 ga 0 86 galvanized steel construction Shipped loose for field attachment Slip and drive connection 3 4 14 dual densit...

Страница 46: ...ustic attenuation 22 ga 0 86 coated steel perforated baffles encapsulate fiberglass acoustic media Internal Steri Liner insulation on top and bottom optimizes sound reduction and eliminates need for external field applied thermal duct wrap Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 20 ga 1 00 zinc coated steel casing Uninsulated Left or right hand connection De...

Страница 47: ... 3 4 19 dual density insulation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal Options and Accessories q Steri liner q Fiber free liner q Solid metal liner q 1 25 liner qSide access door q 24 VAC control transformer q Toggle disconnect switch q Hanger brackets q ...

Страница 48: ...kage Continuous internal insulation reduces insulation seams and minimizes airflow disturbance Supplied with same liner as basic unit q Integral Sound Attenuator Dimensional Data Unit Size W H FF Nominal Outlet Size 4 5 6 12 305 8 203 4 5 6 102 127 152 7 8 12 305 10 254 7 8 178 203 9 10 14 356 12 1 2 318 9 10 229 254 12 16 406 15 381 12 305 14 20 508 17 1 2 445 14 356 16 24 610 18 457 16 406 24 x ...

Страница 49: ...HWC112 5 1 2 114 3 1 2 89 3 8 10 1 25 7 8 22 V31HWC212 5 1 2 114 3 1 2 89 3 8 10 3 8 10 7 8 22 14 20 508 17 1 2 445 V31HWC114 5 1 2 114 3 1 2 89 3 8 10 1 25 7 8 22 V31HWC214 5 1 2 114 4 3 4 121 7 8 22 7 8 22 7 8 22 16 24 610 17 1 2 445 V31HWC116 5 1 2 114 3 1 2 89 9 16 14 1 3 16 30 7 8 22 V31HWC216 5 1 2 114 4 3 4 121 7 8 22 7 8 22 7 8 22 24 x 16 17 1 2 445 38 965 V31HWC124 5 127 4 3 4 121 9 16 14...

Страница 50: ...bs Water Volume gal Dry Coil Weight lbs Water Weight lbs Water Volume gal Dry Coil Weight lbs Water Weight lbs Water Volume gal Dry Coil Weight lbs Water Weight lbs Water Volume gal 4 5 6 5 27 0 16 0 02 6 47 0 40 0 05 9 65 0 61 0 08 10 75 0 75 0 10 7 8 6 05 0 19 0 03 7 64 0 47 0 06 11 45 1 09 0 15 12 28 0 88 0 12 9 10 7 08 0 23 0 03 9 25 0 58 0 08 13 59 0 87 0 12 15 75 1 11 0 15 12 9 13 0 46 0 06 ...

Страница 51: ...nstruction Supplied with balancing tees Rectangular discharge with slip and drive cleat duct connection Full NEMA 1 type controls enclosure for factory mounted controls 3 4 19 dual density insulation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right h...

Страница 52: ...rge Sound Attenuator loose Shipped loose for field attachment Slip and drive connection Supplied as standard with same liner as basic unit q AT313 3 916 Long Standard q AT315 5 1524 Long Optional q Special Features ____________________ Unit Size W H Hot Water Coil FF Outlet Size L 1 2 Row L 3 4 Row 4 5 6 12 305 8 203 5 127 7 1 2 191 4 5 6 102 127 152 7 8 12 305 10 254 5 127 7 1 2 191 7 8 178 203 9...

Страница 53: ...ot affected by position Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q Digital Nailor EZvav q Digital by others q Analog by Nailor See separate submittal DIMENSION L 1 OR 2 ROW COILS L 5 127...

Страница 54: ...se Shipped loose for field attachment Slip and drive connection Supplied as standard with same liner as basic unit q AT313 3 916 Long Standard q AT315 5 1524 Long Optional q Special Features ____________________ Dimensional Data Unit Size W H AD Hot Water Coil FF Nominal Outlet Size L 1 2 row L 3 4 row 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 8 203 10 14 356 12 1 2 318 12 305 5 127 7 1 2 191 10 ...

Страница 55: ...arge with slip and drive cleat duct connection Full NEMA 1 type controls enclosure for factory mounted controls 3 4 19 dual density insulation exposed edges coated to prevent air erosion Meets the requirements of NFPA 90A and UL 181 Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airf...

Страница 56: ... END VIEW q AT Discharge Sound Attenuator loose Shipped loose for field attachment Slip and drive connection Supplied as standard with same liner as basic unit q AT313 3 916 Long Standard q AT315 5 1524 Long Optional q Special Features ____________________ Dimensional Data Unit Size W H AD Hot Water Coil FF Nominal Outlet Size L 1 2 row L 3 4 row 8 12 305 12 1 2 318 12 305 5 127 7 1 2 191 8 203 10...

Страница 57: ...UL 181 Right hand controls location is standard shown when looking in direction of airflow Optional left hand controls mounting is available Hot Water Coil Section 1 2 13 Copper tubes and aluminum ripple fins 10 per inch 1 2 3 or 4 row Left or right hand connection Determined by looking in direction of airflow RH illustrated 1 2 13 7 8 22 or 1 3 8 35 O D male solder sweat connections Controls q By...

Страница 58: ...nit q Integral Sound Attenuator plus Hot Water Coil Dimensional Data 4 102 H END VIEW NOM 1 8 3 2 51 W SIDE VIEW H L 36 914 OR 59 1499 AD W SIDE VIEW END VIEW OPTIONAL ACCESS DOOR q FF Round Discharge Collar q AT Discharge Sound Attenuator loose 22 ga 0 86 galvanized steel construction Shipped loose for field attachment Slip and drive connection 3 4 14 dual density fiberglass insulation exposed ed...

Страница 59: ...sity and inherent structure of the flame attenuated glass fiber blankets are highly effective in reducing thermal transfer Tuf Skin readily withstand damage from mechanical abrasion during assembly and from air erosion in service INSULATION CHARACTERISTICS Material Dual density fiberglass surface treated to prevent erosion Thickness 3 4 19 1 25 Density 4 0 lb cu ft 64 kg m3 skin 1 5 lb cu ft 24 kg...

Страница 60: ...ASTM E84 and UL 723 Flame Smoke 25 50 NFPA 90A and 90B ASTM C 209 ASTM C 665 ACOUSTICAL PERFORMANCE Correction factors to cataloged sound power level data standard liner are shown below Single Duct Terminal Units 3000 Series Basic Unit All sizes Octave Band 2 3 4 5 6 7 NC Impact Center Frequency Hz 125 250 500 1000 2000 4000 Average Discharge Sound 0 0 0 0 0 0 0 Radiated Sound 1 2 2 3 3 3 2 Single...

Страница 61: ... 181 Class I ASTM E84 and UL 723 Flame Smoke 25 50 NFPA 90A and 90B ASTM C 1071 Air Velocity 2000 fpm max ASTM C 665 ASTM C 1338 G21 and G22 Fungi and Bacteria Resistance ACOUSTICAL PERFORMANCE Correction factors to cataloged sound power level data standard liner are shown below Single Duct Terminal Units 3000 Series Basic Unit All sizes Octave Band 2 3 4 5 6 7 NC Impact Center Frequency Hz 125 25...

Страница 62: ...FPA 90A and 90B ASTM C 1071 Air Velocity 2000 fpm max ASTM C 665 ACOUSTICAL PERFORMANCE Correction factors to cataloged sound power level data standard dual density insulation are shown below Single Duct Terminal Units 3000 Series Basic Unit All sizes Octave Band 2 3 4 5 6 7 NC Impact Center Frequency Hz 125 250 500 1000 2000 4000 Average Discharge Sound 0 0 0 0 0 0 0 Radiated Sound 1 2 2 3 3 3 2 ...

Страница 63: ...t velocity of 2000 fpm 10 2 m s When digital or other controls are mounted by Nailor but supplied by others these values are guidelines only based upon experience with the majority of controls currently available Controls supplied by others for factory mounting are configured and calibrated in the field Airflow settings on pneumatic and analog controls supplied by Nailor are factory preset when pr...

Страница 64: ...bsorption or duct attenuation Dash in space indicates sound power level is less than 20 dB or equal to background 5 Minimum inlet Ps is the minimum operating pressure requirement of the unit damper full open and the difference in static pressure from inlet to discharge of the unit 6 Asterisk in space indicates that the minimum inlet static pressure requirement is greater than 0 5 w g 125 Pa at rat...

Страница 65: ...33 33 37 69 64 47 36 35 41 69 65 51 38 37 44 70 68 54 41 39 48 9 1400 661 0 01 2 67 62 52 49 50 49 69 64 53 48 51 51 72 67 56 52 52 53 75 69 59 53 53 56 78 73 62 55 55 58 80 76 64 56 55 60 1150 543 0 01 2 59 56 46 43 42 39 65 59 48 45 44 44 69 62 52 47 46 47 74 65 55 49 48 51 76 69 57 50 49 52 78 71 59 50 50 54 900 425 0 01 2 55 52 41 39 34 30 64 56 45 43 41 41 68 60 48 44 43 44 72 64 51 45 44 48 ...

Страница 66: ...0 260 0 01 2 23 26 28 24 28 32 400 189 0 01 2 23 23 24 20 23 26 250 118 0 01 2 20 8 1100 519 0 02 4 20 25 28 33 36 20 25 29 31 35 900 425 0 01 3 23 26 30 34 23 26 29 33 700 330 0 01 2 23 25 30 33 21 24 26 31 500 236 0 01 2 23 24 28 21 23 26 9 1400 661 0 01 2 21 25 28 33 36 20 20 23 28 34 38 1150 543 0 01 2 20 26 29 31 21 25 31 35 900 425 0 01 2 24 26 29 23 28 31 650 307 0 01 2 23 23 25 20 23 26 10...

Страница 67: ...9 53 49 39 39 36 61 55 52 43 43 40 9 1400 661 0 01 2 51 46 46 44 37 35 52 47 46 41 38 35 57 53 49 42 37 35 64 58 53 47 41 37 66 63 57 50 43 40 69 67 61 54 47 44 1150 543 0 01 2 50 45 44 41 34 34 51 46 45 40 36 33 56 52 47 41 36 34 62 56 51 45 39 37 64 61 55 49 42 39 67 64 59 52 46 43 900 425 0 01 2 48 40 39 36 30 29 50 45 42 37 32 30 56 50 45 40 35 33 60 54 49 44 39 36 63 58 52 47 41 38 64 61 56 5...

Страница 68: ...imate inlet velocity of 2000 fpm 10 2 m s When digital or other controls are mounted by Nailor but supplied by others these values are guidelines only based upon experience with the majority of controls currently available Controls supplied by others for factory mounting are configured and calibrated in the field Airflow settings on pneumatic and analog controls supplied by Nailor are factory pres...

Страница 69: ...uct end reflection energy as part of the standard rating Including the duct end correction provides sound power levels that would normally be transmitted into an acoustically non reflective duct The effect of including the energy correction to the discharge SWL is higher sound power levels when compared to previous AHRI certified data For more information on duct end reflection calculations see AH...

Страница 70: ...60 55 78 72 72 71 62 57 80 74 75 73 64 60 82 77 77 75 67 63 84 79 79 77 70 66 1250 590 0 01 2 67 62 62 61 54 49 73 67 66 64 57 53 75 70 69 67 60 56 78 73 73 70 63 59 80 75 75 72 65 62 83 77 76 74 68 64 900 425 0 01 2 62 57 54 51 44 37 68 62 60 58 53 49 71 66 63 62 55 52 75 69 67 65 58 55 77 72 70 67 61 58 79 75 73 70 65 62 675 319 0 01 2 57 51 48 44 37 30 64 59 56 54 49 44 69 64 60 58 53 48 73 68 ...

Страница 71: ...7 49 44 81 76 72 69 51 46 84 78 75 71 53 49 1250 590 0 01 2 66 59 59 55 39 36 72 64 63 59 42 37 74 70 66 62 44 39 77 72 69 64 46 42 79 75 71 66 48 45 82 77 73 68 51 47 900 425 0 01 2 61 55 49 45 28 23 67 61 56 51 35 30 70 65 59 55 38 34 74 69 63 58 41 38 76 71 66 60 44 41 78 73 69 63 47 44 675 319 0 01 2 56 49 43 38 23 20 64 58 52 47 30 25 69 62 56 51 35 31 73 66 60 55 39 36 75 68 63 57 42 39 75 7...

Страница 72: ...8 1250 590 0 01 2 25 29 33 35 38 24 29 31 35 37 20 22 26 33 36 900 425 0 01 2 24 28 31 35 23 28 30 33 23 28 31 675 319 0 01 2 23 28 30 33 23 28 30 31 20 25 26 450 212 0 01 2 23 24 25 21 23 24 20 22 10 1850 873 0 01 2 24 31 34 36 38 39 24 30 31 34 36 38 22 22 26 31 33 37 1650 779 0 01 2 20 28 31 35 37 39 28 31 33 35 37 20 25 30 31 36 1100 519 0 01 2 21 25 28 31 35 21 25 29 31 21 24 25 31 825 389 0 ...

Страница 73: ...590 0 01 2 51 46 45 42 35 35 51 46 46 41 37 34 56 52 48 42 36 34 63 57 52 46 40 37 65 62 56 50 43 40 68 65 60 53 46 44 900 425 0 01 2 48 40 39 36 30 29 50 45 42 37 32 30 56 50 45 40 35 33 60 54 49 44 39 36 63 58 52 47 41 38 64 61 56 50 44 42 675 319 0 01 2 47 37 31 29 22 49 41 36 31 28 25 55 48 42 37 32 30 58 52 46 41 35 33 60 56 50 44 38 36 60 57 52 47 41 39 450 212 0 01 2 24 48 40 33 30 26 24 53...

Страница 74: ...et NEC code requirements A minimum of 1 w g 25 Pa of downstream static pressure is required to ensure proper operation of the heater To avoid possible nuisance tripping of the thermal cutouts due to insufficient airflow a minimum airflow of 70 cfm 33 l s per kilowatt must be maintained Model 30RE Electric Coil Limitations Minimum required airflow must be the greater of the air volume listed or 70 ...

Страница 75: ...t velocity of 2000 fpm 10 2 m s When digital or other controls are mounted by Nailor but supplied by others these values are guidelines only based upon experience with the majority of controls currently available Controls supplied by others for factory mounting are configured and calibrated in the field Airflow settings on pneumatic and analog controls supplied by Nailor are factory preset when pr...

Страница 76: ...ctions for room absorption or duct attenuation Dash in space indicates sound power level is less than 20 dB or equal to background 0LQLPXP LQOHW 3V LV WKH PLQLPXP RSHUDWLQJ SUHVVXUH requirement of the unit damper full open and the difference in static pressure from inlet to discharge of the unit 6 Asterisk in space indicates that the minimum inlet static pressure requirement is greater than 0 5 w ...

Страница 77: ...6 0 01 2 55 46 37 29 21 61 55 47 39 26 32 65 60 51 43 28 37 69 64 55 46 30 41 70 66 58 48 31 45 70 68 61 51 33 48 9 1400 661 0 01 2 66 62 56 53 47 47 70 66 60 55 52 53 73 69 62 57 52 56 76 71 65 58 53 59 78 74 67 60 54 60 80 77 69 62 54 62 1150 543 0 01 2 62 56 49 45 36 35 66 61 55 49 45 46 69 64 58 51 46 49 73 67 60 53 47 53 75 70 63 55 47 54 77 73 65 56 48 56 900 425 0 01 2 58 52 43 39 28 27 63 ...

Страница 78: ... 21 26 30 35 550 260 0 04 10 21 25 28 24 28 32 400 189 0 01 2 20 21 23 20 23 26 250 118 0 01 2 20 8 1100 519 0 02 4 21 24 28 30 34 37 20 25 29 31 35 900 425 0 01 3 20 24 28 31 35 23 26 29 33 700 330 0 01 2 21 26 30 34 21 24 26 31 500 236 0 01 2 23 25 28 21 23 26 9 1400 661 0 01 2 24 28 30 34 37 20 20 23 28 34 38 1150 543 0 01 2 21 25 29 33 21 25 31 35 900 425 0 01 2 23 26 30 23 28 31 650 307 0 01 ...

Страница 79: ... 48 44 35 34 31 58 51 47 37 37 33 59 53 49 39 39 36 61 55 52 43 43 40 9 1400 661 0 01 2 51 46 46 44 37 35 52 47 46 41 38 35 57 53 49 42 37 35 64 58 53 47 41 37 66 63 57 50 43 40 69 67 61 54 47 44 1150 543 0 01 2 50 45 44 41 34 34 51 46 45 40 36 33 56 52 47 41 36 34 62 56 51 45 39 37 64 61 55 49 42 39 67 64 59 52 46 43 900 425 0 01 2 48 40 39 36 30 29 50 45 42 37 32 30 56 50 45 40 35 33 60 54 49 44...

Страница 80: ...abulate Radiated NC levels The following table provides the calculation method for the radiated sound total attenuation values based on AHRI Standard 885 The ceiling space effect assumes the following conditions 1 5 8 16 tile 20 lb ft3 320 kg m3 density 2 The plenum is at least 3 feet 914 deep 3 The plenum space is either wide over 30 feet 9 m or lined with insulation 4 The ceiling has no signific...

Страница 81: ...15 8 13 8 11 7 9 7 7 6 kW MBH GPM l s 63 47 32 19 13 09 10 7 5 5 3 2 1 CFM l s 400 550 700 850 1000 1150 1300 1450 1600 1750 1900 2050 2200 189 260 330 401 472 543 613 684 755 826 897 967 1038 130 120 110 100 90 80 70 60 50 40 30 20 38 1 35 2 32 2 29 3 26 4 23 4 20 5 17 6 14 7 11 7 8 8 5 9 kW MBH GPM l s 63 47 32 19 13 09 Altitude Correction Factors Correction factors at other entering conditions ...

Страница 82: ... 21 4 19 0 16 7 14 4 12 0 9 7 kW MBH GPM l s 63 47 32 19 13 09 10 7 5 5 3 2 1 CFM l s 500 700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 236 330 425 519 613 708 802 897 991 1085 1180 1274 161 152 143 134 125 116 107 98 89 80 71 62 53 44 35 47 2 44 5 41 9 39 3 36 6 34 0 31 4 28 7 26 1 23 4 20 8 18 2 15 5 12 9 10 3 kW MBH GPM l s 63 47 32 19 13 09 Altitude Correction Factors Correction factors...

Страница 83: ... 9 22 0 19 0 16 1 13 2 10 3 kW MBH GPM l s 63 47 32 19 13 09 10 7 5 5 3 2 1 CFM l s 700 950 1200 1450 1700 1950 2200 2450 2700 2950 3200 3450 3700 330 448 566 684 802 920 1038 1156 1274 1392 1510 1628 1746 193 183 173 163 153 143 133 123 113 103 93 83 73 63 53 43 56 5 53 6 50 7 47 8 44 8 41 9 39 0 36 0 33 1 30 2 27 2 24 3 21 4 18 5 15 5 12 6 kW MBH GPM l s 63 47 32 19 13 09 Altitude Correction Fac...

Страница 84: ...2 7 46 9 41 0 35 2 29 3 23 4 17 6 11 7 kW MBH GPM l s 95 63 47 32 19 09 15 10 7 5 5 3 1 CFM l s 1000 1700 2400 3100 3800 4500 5200 5900 6600 7300 8000 472 802 1133 1463 1793 2124 2454 2784 3115 3445 3775 370 350 330 310 290 270 250 230 210 190 170 150 130 110 90 70 50 108 4 102 6 96 7 90 8 85 0 79 1 73 3 67 4 61 5 55 7 49 8 44 0 38 1 32 2 26 4 20 5 14 7 kW MBH GPM l s 95 63 47 32 19 09 Altitude Co...

Страница 85: ...50 300 350 400 450 500 24 47 71 94 118 142 165 189 212 236 38 35 32 29 26 23 20 17 14 11 8 5 11 1 10 3 9 4 8 5 7 6 6 7 5 9 5 0 4 1 3 2 2 3 1 5 kW MBH GPM l s 3 2 1 5 1 0 5 19 13 09 06 03 Altitude Correction Factors Correction factors at other entering conditions 1 Capacities are in MBH kW thousands of Btu per hour kiloWatts 2 MBH kW values are based on a t temperature difference of 125 F 69 C betw...

Страница 86: ...06 03 5 4 3 2 1 5 1 0 5 CFM l s 200 300 400 500 600 700 800 900 1000 94 142 189 236 283 330 378 425 472 67 63 59 55 51 47 43 39 35 31 27 23 19 15 19 6 18 5 17 3 16 1 14 9 13 8 12 6 11 4 10 3 9 1 7 9 6 7 5 6 4 4 kW MBH GPM l s 32 25 19 13 09 06 03 Altitude Correction Factors Correction factors at other entering conditions 1 Capacities are in MBH kW thousands of Btu per hour kiloWatts 2 MBH kW value...

Страница 87: ...BH GPM l s 47 32 19 13 09 03 7 5 5 3 2 1 0 5 CFM l s 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 142 189 236 283 330 378 425 472 519 566 613 661 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 26 4 24 9 23 4 22 0 20 5 19 0 17 6 16 1 14 7 13 2 11 7 10 3 8 8 7 3 5 9 kW MBH GPM l s 47 32 19 13 09 03 Altitude Correction Factors Correction factors at other entering conditions 1 Capacities are in ...

Страница 88: ...FM 47 94 189 283 472 944 1888 l s AIR PRESSURE DROP 10 0 8 0 6 0 4 0 2 0 1 0 0 8 0 6 0 4 0 2 0 1 0 08 0 06 0 04 0 02 0 01 Pa in w g 2486 1989 1492 994 497 249 199 149 99 50 25 20 15 10 5 2 4 ROW 4 ROW Unit Size 24 x 16 1 ROW 2 ROW 3 ROW Water Pressure Drop WATER FLOW HEAD LOSS WATER PRESSURE DROP 1 2 4 6 8 10 20 GPM 06 13 25 38 50 63 1 26 l s 10 0 8 0 6 0 4 0 2 0 1 0 0 8 0 6 0 4 0 2 0 1 kPa ft H2O...

Страница 89: ...R FLOW HEAD LOSS WATER PRESSURE DROP 1 2 4 6 8 10 GPM 06 13 25 38 50 63l s 10 0 8 0 6 0 4 0 2 0 1 0 0 8 0 6 0 4 0 2 0 1 kPa ft H2O 29 8 23 9 17 9 11 9 6 0 3 0 2 4 1 8 1 2 0 6 0 3 AIR PRESSURE DROP Air Pressure Drop AIRFLOW 100 200 400 600 1000 2000CFM 47 94 189 283 472 944 l s 10 0 8 0 6 0 4 0 2 0 1 0 0 8 0 6 0 4 0 2 0 1 0 08 0 06 0 04 0 02 0 01 Pa in w g 2486 1989 1492 994 497 249 199 149 99 50 2...

Страница 90: ...e mounting base 3 Fasten the mounting base directly to a 2 x 4 inch 51 x 102 mm outlet box or a backplate with the Allen screws toward the floor 4 Insert the Ethernet cable coming from the base into the sensor 5 Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw brackets Be careful not to pinch any wiring 6 Turn the Allen screws counterclockwise un...

Страница 91: ...ion sensing coverage False detections may be triggered by any of the following conditions The temperature inside the detection range suddenly changes because of the entry of cold or warm air from an air conditioning or heating unit The sensor being directly exposed to sunlight an incandescent light or other source of far infrared rays Small animal movement Changing room set points Room set points ...

Страница 92: ...thecontrollerendofthecableintotheT statconnector 4 Connect the airflow sensors Connect the airflow sensor on the VAV box to the airflow ports on the controller Use 0 25 in FR tubing 5 Connect auxiliary equipment optional Other VAV equipment such as fans heaters reheat valves and discharge air temperature sensors connect at the green terminals If the controller is part of a BACnet network wire it t...

Страница 93: ...ensor temporarily connect an STE 8001W36 as a service tool To get started Press together the up and down buttons to start configuration or balancing Enter Password 2 if required New installations do not have a password Press the up or down buttons to move between functions or change values Press the set point button to choose a selection or save a value CNFG The main configuration parameters for t...