SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
Standard Features:
• Bottom mount controls location with
vertical drive shaft (option code OB).
• 22 ga. (0.86) zinc coated steel casing,
mechanically sealed, low leakage
construction.
• 16 ga. (1.61) corrosion-resistant steel
inclined opposed blade damper with
extruded PVC seals (single blade on size
4, 5, 6). 45
°
rotation, CW to close.Tight
close-off. Damper leakage is less than
2% of the terminal rated airflow at 3" w.g.
(750 Pa).
•1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the shaft
shows damper position.
• Multi-point averaging Diamond Flow
Sensor. Aluminum construction. Supplied
with balancing tees.
• Rectangular discharge with slip and
drive cleat duct connection.
• Full NEMA type-1 controls enclosure for
factory mounted controls.
•
3/4" (19), dual density insulation,
exposed edges coated to prevent air
erosion. Meets the requirements of NFPA
90A and UL 181.
Hot Water Coil Section:
• 1/2" (13) Copper tubes and aluminum
ripple fins, 10 per inch.
• 1, 2, 3 or 4 row.
•
Left or right hand connection.
Determined by looking in direction of
airflow (RH illustrated).
• 1/2" (13), 7/8" (22) or 1 3/8" (35) O.D.
male solder sweat connections.
Controls:
q
Digital (by others).
q
Analog (by Nailor).
See separate submittal.
Options and Accessories:
q
Steri-liner.
q
Fiber-free liner.
q
Solid metal liner.
q
1" (25) liner.
q
Bottom access door.
q
24 VAC Control transformer.
q
Toggle disconnect switch.
q
Hanger brackets.
q
Controls enclosure for field mounted
controls.
q
Dust tight enclosure seal.
q
Special Features:
___________________________ .
DATE
B SERIES
SUPERSEDES DRAWING NO.
3 - 30 - 17
3000
8 - 3 - 09
D30RW-2
Page 1 of 2.
Dimensions are in inches (mm).
SINGLE DUCT TERMINAL UNIT W/HOT WATER REHEAT
DIGITAL OR ANALOG CONTROLS • CONSTANT OR
VARIABLE VOLUME • PRESSURE INDEPENDENT
MODELS: D30RW AND A30RW WITH BOTTOM MOUNT
CONTROLS LOCATION (OPTION OB)
OPTIONAL
ACCESS DOOR
SLIP AND DRIVE
CONNECTION
14" (356)
5 1/2"
(140)
6"
(152)
1/2"
(13)
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
MULTI-POINT
AVERAGING
FLOW SENSOR
11" (279)
22 1/2" (572)
W
H
DAMPER
DRIVESHAFT
L
W
H
DIMENSION "L"
1 OR 2 ROW COILS, L = 5" (127)
3 OR 4 ROW COILS, L = 7" 1/2 (191)
CONTROLS
ENCLOSURE
FOR FACTORY
MOUNTED CONTROLS
AIRFLOW
*
Maximum airflow limit is based upon 1.5" w.g. (373 Pa) max. differential pressure signal from Diamond Flow Sensor.
Unit
Size
Airflow Range*
cfm (I/s)
W
H
Inlet Size
Coil Connections
1 Row
2 Row
3 Row
4 Row
4
0 – 225 (0 – 106)
10 (254)
10 (254)
3 7/8 (98) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
5
0 – 400 (0 – 189)
10 (254)
10 (254)
4 7/8 (124) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
6
0 – 550 (0 – 260)
10 (254)
10 (254)
5 7/8 (149) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
7
0 – 800 (0 – 378)
12 (305)
12 1/2 (318)
6 7/8 (175) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
8
0 – 1100 (0 – 519)
12 (305)
12 1/2 (318)
7 7/8 (200) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
9
0 – 1400 (0 – 661)
14 (356)
12 1/2 (318)
8 7/8 (225) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
10
0 – 1840 (0 – 868)
14 (356)
12 1/2 (318)
9 7/8 (251) Round
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
12
0 – 2500 (0 – 1180)
18 (457)
12 1/2 (318)
12 15/16 x 9 13/16 (329 x 249) Oval
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
14
0 – 3125 (0 – 1475)
24 (610)
12 1/2 (318)
16 1/16 x 9 13/16 (408 x 249) Oval
1/2 (13) 7/8 (22) 7/8 (22)
7/8 (22)
16
0 – 3725 (0 – 1758)
28 (711)
12 1/2 (318)
19 3/16 x 9 13/16 (487 x 249) Oval
7/8 (22) 7/8 (22) 7/8 (22)
7/8 (22)
24 x 16
0 – 8330 (0 – 3931)
38 (965)
18 (457)
23 7/8 x 15 7/8 (606 x 403) Rect.
7/8 (22) 7/8 (22) 1 3/8 (35) 1 3/8 (35)
Dimensional Data