Bus Voltage Group
Low DC Bus Enable -
Epsilon Only
This parameter’s default setting is enabled. When enabled, the drive will detect a low DC bus
at 60 VDC and will log a Low DC Bus Fault if a power down is not completed after the low
DC bus is detected. Setting this to disabled will disable the Low DC Bus Voltage Fault. This
will allow the drive to operate at a DC bus voltage below 60 VDC as long as the logic power
is supplied by the A.P.S. (Alternate Power Supply).
Figure 50:
Epsilon Bus Voltage View
Encoder State Fault Enable
This parameter’s default setting is enabled. When enabled, the drive will detect encoder state
faults. Refer to Fault Codes in the Diagnostic and Troubleshooting section of this manual. The
drive will not detect Encoder State faults when the fault is disabled. Disabling encoder faults
is necessary for some types of programable encoders where the state transitions are not
always deterministic.