14 • PMAC
II
I&O Manual
fields. You may have to turn on Full Options
mode to see these fields (press
(6
in Ein-
stein, or press
6
+
in E2, then press
"
and
!
to leave and return to this screen.
The fields should then be visible).
3. Press
B
(NEXT TAB) to advance to the
).
4.4.2.3. Screen 3: Inputs
1. If you are using temperature and humidity
sensors to calculate the dewpoint, enter the
board and point input locations for these de-
vices here. If you are using a dewpoint sen-
sor, enter the board and point input location
for the sensor here.
2. Press
B
(NEXT TAB) to advance to the
Outputs Setup screen (
4.4.2.4. Screen 4: Outputs
1. In the
OUTPUT
field, enter the point on the
8DO board (located in the PMAC II) that cor-
responds to the anti-sweat channels you wish
to see which point controls which
channels
.
Figure 4-6
- Anti-Sweat Inputs Setup Screen
Figure 4-7
- Anti-Sweat Outputs Setup Screen
8DO Points for 16
Channel
Anti-Sweat Channel
Circuits
1
7, 8
2
5, 6
3
3, 4
4
1, 2
5
15, 16
6
13, 14
7
11, 12
8
9, 10
Table 4-1
- 8DO Board Points to PMAC II 16 Channel
8DO Points for 20
Channel
Anti-Sweat Channel
Circuits
1
1, 2
2
3, 4
3
5, 6
4
7, 8
5
9, 10
6
11, 12
7
13, 14, 17, 18
8
15, 16, 19, 20
Table 4-2
- 8DO Board Points to PMAC II 20 Channel
8DO Points for 28
Channel
Anti-Sweat Channel
Circuits
1
1, 2, 15, 16
2
3, 4, 17, 18
3
5, 6, 19, 20
4
7, 21
5
8, 9, 22, 23
6
10, 11, 24, 25
7
12, 13, 26, 27
8
14, 28
Table 4-3
- 8DO Board Points to PMAC II 28 Channel