background image

BEC and RMCC Page Layout

Configuring RMCC, BEC, Einstein and E2 • 9

4

Configuring RMCC, 

BEC, Einstein and E2

A BEC, RMCC, Einstein, or E2 is capable of control-

ling eight anti-sweat heater circuits. BECs allow the eight 

heaters to be controlled in two different zones, RMCCs one 

zone, and Einstein & E2’s eight zones. Each zone requires 
its own dewpoint sensor and setpoint(s). A humidity sensor 

and temperature sensor may be used in lieu of a dewpoint 

sensor.

The following sections outline the procedure for setting 

up anti-sweat control in the BEC, RMCC, Einstein, and E2. 

For detailed information on system programming, users 
should consult the site controller’s user documentation. 

4.1.

BEC and RMCC Page Layout

Each data screen used in anti-sweat setup is shown in 

sections to follow. Data ranges for data fields—the infor-

mation supplied in the help prompt lines—are displayed in 

brackets and bold type 

[-99° - 99°] 

either at the heading for 

the particu-lar field description, or—when a heading does 

not exist— within the body of the description. Suggested or 

default values for a particular entry are always shown in 
brackets and bold type immediately following the data 

range 

[-99° - 99°] [-15.5]

.

4.2.

Programming the BEC

4.2.1. Input Definitions

From the Main Menu, press ’7 1’ to access the Input 

Definitions screen.

Define 16AI or 8IO board and point addresses for the 

anti-sweat humidity and temperature sensors. Use the 
down arrow keys to locate the following inputs: (ASC 

HUM1, ASC TEMP 1, ASC HUM2, ASC TEMP 2) and 

the anti-sweat override inputs (ASC #1 OVRD - ASC #8 
OVRD).  Refer to 

P/N 026-1103, Building Environmental 

Control I&O Manual, 

Section 6.10.1., 

Input Definition

, for 

more information.

4.2.2. Output Definitions

From the Main Menu, press ’7 2’ to access the Out-

put Definitions screen.

Define 8RO and/or 8DO board and point addresses for 

the anti-sweat heater zones. Use the down arrow keys to lo-
cate the following outputs: (ANTI-SWT 1 - ANTI-SWT 8). 

Refer to 

P/N 026-1103, Building Environmental Con-trol 

I&O Manual, 

Section 6.10.2., 

Output Definition

, for more 

information.

4.2.3. Dewpoint/Humidity Offsets

From the Main Menu, press ’3 2 1’ to access the 

Dewpoint/Humidity Offsets screen.

If the dewpoint cell or relative humidity sensor is 

known to read high or low, offsets may be specified in the 

Dewpoint Offset and Humidity Offset fields to correctly 

calibrate the sensors. Users may enter a value from -20% to 
20% or from -20° to 20°.

4.2.4. Outputs Setup

From the Main Menu, press ’3 2 2’ to access the 

Anti-Sweat Outputs Setup screen.

Setup data such as heater interval times, names, and 

board and circuit assignments are entered in the Anti-Sweat 

Outputs Setup screen.

ON/OFF Interval [1 - 999 sec.] [10 sec.]

All anti-sweat circuits pulse heaters ON for a percent-

age of a defined time interval. This interval is entered in the 

ON/OFF Interval field. If an 8DO board is being used, the 
value should be less than 240 seconds.

Содержание 851-1000

Страница 1: ...Pulse Modulating Anti Sweat Control PMAC II Installation and Operation Manual 026 1501 Rev 6 ...

Страница 2: ...A Phone 770 425 2724 Fax 770 425 9319 Please Note This manual covers the PMAC II P N 851 1000 family of anti sweat panels Information on the PMAC II Solo P N 851 1100 anti sweat controller is contained in P N 026 1503 PMAC II Solo Installation and Operation Manual ...

Страница 3: ...ALARMING ALL MODELS 8 3 2 1 Overheat Warning 8 3 2 2 Panel Overheat Shutdown 8 4 CONFIGURING RMCC BEC EINSTEIN AND E2 9 4 1 BEC AND RMCC PAGE LAYOUT 9 4 2 PROGRAMMING THE BEC 9 4 2 1 Input Definitions 9 4 2 2 Output Definitions 9 4 2 3 Dewpoint Humidity Offsets 9 4 2 4 Outputs Setup 9 4 2 5 Setpoints 10 4 3 PROGRAMMING THE RMCC 10 4 3 1 Input Definitions 10 4 3 2 Output Definitions 10 4 3 3 Dewpoi...

Страница 4: ...may have 16 20 or 28 heater channels available Each channel supports a load of up to 16 amps The PMAC II relies on a site controller to control anti sweat heater ON percentage based on the in store dew point The PMAC II panel is compatible with the Building Environmental Control BEC Refrigeration Monitor and Case Control RMCC and Einstein RX or BX or an E2 site controllers The RMCC is capable of c...

Страница 5: ...air flow The room s ambient temperature should always be below 100 F Figure 2 1 and Figure 2 2 have the mounting dimensions 2 Provide 120 VAC 15 amp circuit to the PMAC II panel through a store circuit break er See the layout design in Figure 2 3 3 Provide power to the case heaters from the store circuit breaker panel through the PMAC II panel terminal strip using 10 12 AWG wire as shown in Figure...

Страница 6: ...ity must be respected while mak ing these connections 2 1 1 1 Single Channel Expansion Ports The 20 Channel PMAC has two expansion ports Fig ure 2 6 and the 28 Channel PMAC has six single expan sion ports Figure 2 7 These expansion ports can be used to attach single channel PMACs if desired P N 851 1010 NOTE When running power to the case heat ers include the neutral lead in the same con duit as t...

Страница 7: ...rovide continuous voltage to the case heaters during network com munication loss The fail safe dip switches should always remain in the UP position to ensure voltage is always pro vided to the case heaters If the switches are set in the DOWN position no voltage will be sent to the heaters dur ing network communication loss 2 2 3 Network Jumpers The network jumpers JU1 JU2 and JU3 define whether th...

Страница 8: ...24VAC center tap ground from the PMAC II transformer and converts it to 12VDC to drive the PMAC II relays Network Connection RS 485 Network communication is provided through the network communication connection as shown in Fig ure 2 8 Table 2 1 and described in the Location and Wir ing sections of this manual ...

Страница 9: ... connected to a point on a 16AI or other input board you may configure the controller to generate an alarm or perform some other control func tion to respond to this alarm condition Refer to the control ler s user manual for information on how to do this 3 2 Panel Overheat Alarming All Models The PMAC II has a feature that prevents equipment damage as a result of overheating When the temperature i...

Страница 10: ... for the anti sweat humidity and temperature sensors Use the down arrow keys to locate the following inputs ASC HUM1 ASC TEMP 1 ASC HUM2 ASC TEMP 2 and the anti sweat override inputs ASC 1 OVRD ASC 8 OVRD Refer to P N 026 1103 Building Environmental Control I O Manual Section 6 10 1 Input Definition for more information 4 2 2 Output Definitions From the Main Menu press 7 2 to access the Out put De...

Страница 11: ...circuit s heaters will remain ON at all times Between these dew point values the anti sweat circuit will pulse ON and OFF for a percentage of the time interval defined in the Outputs Setup screen Percent On During All OFF 0 30 0 By default anti sweat circuits operate at 0 when the dewpoint is below the Dewpoint All OFF setpoint If de sired a higher value for All OFF may be specified Percent On Dur...

Страница 12: ... re main OFF at all times The Dewpoint All ON setpoint is the maximum dewpoint above which the anti sweat circuit s heaters will remain ON at all times Between these dew point values the anti sweat circuit will pulse ON and OFF for a percentage of the time interval defined in the Outputs Setup screen Percent On During All OFF 0 30 0 By default anti sweat circuits operate at 0 when the dewpoint is ...

Страница 13: ...g in to the Einstein 2 Press Actions from the Main Status screen 3 Press Control Appl Setup 4 Press Add Control Application 5 Press Look Up and press the DOWN AR ROW key until Anti Sweat is highlighted 6 Press 7 Press the DOWN AR ROW key and enter the desired number of appli cations in the How many field 8 Press to add the Anti Sweat applications 1 Log in to the E2 2 Press I 3 Press Add Delete App...

Страница 14: ...values that will corre spond to the maximum and minimum ON percentages in the FULL ON DEWPOINT and FULL OFF DEWPOINT fields 2 If you wish to limit the minimum and maxi mum output percentages enter the desired limits in the Min Output and Max Output Einstein E2 1 From the Home screen press to select Anti Sweat 2 If you have created more than one application you will be asked to select an applicatio...

Страница 15: ...en 4 Outputs 1 In the OUTPUT field enter the point on the 8DO board located in the PMAC II that cor responds to the anti sweat channels you wish to control See Table 4 1 Table 4 2 and Ta ble 4 3 to see which point controls which channels Figure 4 6 Anti Sweat Inputs Setup Screen Figure 4 7 Anti Sweat Outputs Setup Screen 8DO Points for 16 Channel Anti Sweat Channel Circuits 1 7 8 2 5 6 3 3 4 4 1 2...

Страница 16: ...onal point on the 8DO board you want to control from this application 2b Highlight each output and change the defini tion style to Board Point for E2 press C for Einstein press 2c Enter the board and point number of the 8DO point 2d Continue until all outputs are defined 3 Press H to return to the Home screen For Einstein press HOME to return to the main status screen Setup of the anti sweat appli...

Страница 17: ...t Parts Replacement Parts Fan 120V 120CFM 147 0300 Heat Sink Assembly w Triacs 610 3150 Opto Board Solo 16 and 28 Channel 537 3051 Interface Board 537 3069 8DO Board 810 3050 Opto Board 20 Channel 537 3055 Table 5 1 Replacement Parts and Part Numbers ...

Страница 18: ... Climate Technologies Retail Solutions Inc and or its affiliates collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 02...

Отзывы: