Instruction Manual
D103621X012
4320
January 2018
6
Table 1. Specifications (continued)
Wireless Communication Signal
2.4 GHz, DSSS, IEC 62591 (
Wireless
HART)
Maximum 10 dBm (10 mW) EIRP at 2.46 GHz
Wireless Classifications
Class A digital device, complies with part 15 of the
FCC Rules
Contains FCC ID: LW2RM2510
Contains IC: 2731A‐RM2510
Electromagnetic Compatibility
Meets EN 61326‐1:2013
Immunity—Industrial locations per Table 2 of
the EN 61326‐1 standard. Performance is
shown in table 2 below.
Emissions—Class A & B. Performance is shown in
table 3 below.
ISM equipment rating: Group 1, Class A & B
Vibration Testing
Meets or exceeds vibration levels specified in
ANSI/ISA 75.13.01 1996 (2007):
4 mm peak to peak at 5 Hz,
2 g from 15150 Hz, and
1 g from 150 2000 Hz
European Directive Information
This product complies with the following directives:
ATEX Directive (2014/34/EU)
Electro Magnetic Compatibility (EMC) (2014/30/EU)
Radio Equipment Directive (RED) (2014/53/EU)
Pressure Equipment Directive (PED) (2014/68/EU)
Reduction of Hazardous Substances (RoHS)
(2011/65/EU)
Click or scan to access the
Declaration of Conformity
Operating Temperature Limits
Monitoring
Battery Power:
-40 to 85
_
C (-40 to 185
_
F)
External Power:
-40 to 80
_
C (-40 to 176
_
F)
LCD may not be readable below -20
_
C (-4
_
F)
With Pneumatic Output (On/Off Control)
:
-20 to 50
_
C (-4 to 122
_
F)
Temperature Sensitivity
0.06% change per degree C
Storage Temperature Limits
-40 to 70
_
C (-40 to 158
_
F)
Humidity Limits
10-95% Non‐Condensing Relative Humidity
Electrical Classification
CSA (C/US)
— Intrinsically Safe
ATEX
— Intrinsically Safe
IECEx
— Intrinsically Safe
Electrical Housing
Type 4X, IP66 & IP67
Other Classifications/Certifications
CUTR—
Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
INMETRO
—National Institute of Metrology,
Quality and Technology (Brazil)
NEPSI
—National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE
—Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
TIIS
—Technology Institution of Industrial Safety
(Japan)
or Local Business
Partner for classification/certification specific
information
IEC 61010 Compliance
Meets Pollution Degree 4
Adjustments
Zero and Maximum Span through local interface
Altitude Rating
Up to 2000 meters (6562 feet)
Weight
Monitoring
— 0.57 kg (1.25 lb)
On/Off Control
— 1.6 kg (3.4 lb)
‐continued‐
http://emr.sn/RK7c