Figure 5. Fisher 4320 with Battery Sourced Power Modules
FILTER (2)
2. Insert a user-supplied cable gland or conduit fitting into the housing.
3. Insert the wires through the cable gland/conduit fitting.
WARNING
Wiring connected to the External Power terminals should be rated for +100°C (212°F) max.
Failure to use properly rated wiring can result in personal injury or property damage from fire or explosion.
polarity-insensitive; i.e., you can connect the positive or negative wire to either terminal screw.
terminal following national and local codes and plant standards.
6. Tighten the wiring terminal screws.
7. Close the cover and tighten the instrument cover screws to a torque of 5.6 to 6.7 N•m (50 to 60 lbf•in).