Instruction Manual
D103621X012
4320
January 2018
28
Note
During the manual calibration procedure, the valve is moved to one position and MARKED. The valve is then moved to other end of
travel or rotation and the second position is recorded (MARKED). Earlier calibration points can be used or discarded.
Applying calibration points without changing the valve position will result in the calibration attempt being unused or discarded.
Output (On/Off Control)
Press the right button to access OUTPUT calibration. Press the left button (OK) when prompted to move the valve. This
will set the pneumatic output action to the valve movement direction. The next display instructs you to select the
current state; push the left button to select 100% and the right button to select 0%. When prompted press NEXT to
return to the CALIBRATE menu.
When calibration is complete, the calibration status will be displayed:
SUCCESS—indicates that the calibration procedure was successful.
SPAN HI—indicates that a problem with the high end of travel or rotation was observed. Check the mounting and
magnet assembly placement and re‐attempt calibration.
SPAN LO—indicates that a problem with the low end of travel or rotation was observed. Check the mounting and
magnet assembly placement and re‐attempt calibration.
ERROR SPAN— indicates that the distance between the two marked endpoints was too small to provide a reliable
calibration. See table 5 on page 56 for troubleshooting help.
D
Check the mounting and magnet assembly placement and re-attempt calibration.
D
When using the rotary magnet assembly ensure that the magnet does not go perpendicular to the positioner
feedback slot.
FAILED— indicates that Auto Calibration failed, most likely because the valve failed to move or did not settle in time;
settle time for each position is 5 minutes.
Press the right button to exit the calibration attempt, the display will show UNCHANGED.
Press NEXT to return to the CALIBRATE menu
.
From the CALIBRATE display press NEXT to enter the OUTPUT menu (on/off control only), or to display the EXIT menu.