TROUBLESHOOTING 

Reset Operation

If  a  voltage  spike  or  static  discharge  blanks  out  the  display 
or  causes  erratic  thermostat  operation,  you  may  need  to 
reset  the  thermostat.  To  reset,  the  System  Switch  must  be 
in 

Cool

 or 

Heat

. Simultaneously press 

 and 

 buttons 

for  approximately  10  seconds  until  the  display  goes  blank.  If 
the thermostat has power, has been reset and still does not 
function correctly contact your heating/cooling service person 
or place of purchase.

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan
common problems)

1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or  
    panel loose or not properly installed.

Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety 
interlock or door switch.

No Heat

1. System Switch not set to Heat.

2. Loos connection to thermostat or 
    system
3. Heating System requires service or 
    thermostat requires replacement.

Set System Switch to Heat and raise setpoint above room 
temperature.
Verify thermostat and system wires are securely at-
tached.
Diagnostic: Set System Switch to Heat and raise the set-
point above room temperature. Within a five minutes the 
thermostat should make a soft slick sound. This sound 
usually indicates the thermostat is operating properly. 
If the thermostat does not click, try the reset operation 
listed above. If the thermostat does not click after being 
reset contact your heating and cooling service person 
or place of purchase for a replacement. If the thermostat 
clicks, contact the furnace manufacturer or a service per-
son to verify the heating system is operating correctly.

No Cool

1. System Switch not set to Cool.

2. Loose connection to thermostat or 
    system.
3. Cooling System requires service or 
    thermostat requires replacement

Set System Switch to Cool and lower setpoint below 
room temperature.
Verify thermostat and system wires are securely at-
tached.
Same procedures as diagnostic for No Heat condition 
except set the thermostat to Cool and lower the setpoint 
below the room temperature. There may be up to a five 
minute delay before the thermostat clicks in Cooling if the 
compressor lock-out option is selected in the configura-
tion menu (Item 5). 

Heat, Cool or Fan Runs 
Constantly

1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in Heat/Cool/Fan 
    system.
4. Fan Switch set to Fan On.

Check each wire connection to verify they are not shorted 
or touching together. No bare wire should stick out from 
under terminal screws. Try resetting the thermostat as de-
scribed below. If the condition persists, the manufacturer 
of your system or service person can instruct you on how 
to test the Heat/Cool/ system for correct operation. If the 
system operates correctly, replace the thermostat.

Furnace Cycles Too Fast 
or Too Slow Cooling 
Cycles Too Fast or Too 
Slow (narrow or wide 
temperature swing)

1. The location of the thermostat and/or 
    the size of the Heating or Cooling 
    System may be influencing the cycle 
    rate.

Item 3 (CR Heat) or 4 (CR Cool) in the Configuration 
Menu is the adjustment that controls the cycle rate. If an 
acceptable cycle rate is not achieved using the FA (Fast) 
or SL (Slow) adjustment contact a local service person 
for additional suggestions.

Thermostat Setting and 
Thermometer Disagree

1. Thermostat thermometer setting 
    requires adjustment.

The thermometer can be ad/- degrees as listed in 
item 7 of the Configuration Menu. No other adjustment is 
possible.

Blank Display and/or 
Keypad Not Responding

1. Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the Reset 
Operation listed above.

Содержание 1F86-0244

Страница 1: ...el Programming Choice 1F86 0244 Non Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Operating Ambient 32 to 105 ...

Страница 2: ...on O B TERMINAL SWITCH SELECTION The O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be move...

Страница 3: ...rcuits are in only one of the systems remove the transformer of the system with NO safety circuits NOTE Optional Jumper for Single Stage Heat Pump R C G W Figure 4 Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems Changeover Relay Y O B Compressor Contactor Changeover Relay is energized in COOL when O B switch is in the O position Changeover Relay...

Страница 4: ...isplays current temperature Figure 5 Thermostat display buttons and switches SYSTEM 2 1 3 4 5 6 7 8 9 11 10 9 Service indicatesadiagnosticfaultintheheating cooling system It does not indicate a fault in the thermostat 10 Change Filter is displayed when the system has run for the programmed filter time period as a reminder to change or clean your air filter 11 indicates power level of batteries Cha...

Страница 5: ...gle Stage Heat is Medium Cycle ME For Single Stage Cool the default setting is fast FA To change cycle rate press the and buttons The cycle rate differentials for different settings are MODE Fast Medium Slow FA ME SL SS Heat 0 6 F 0 8 F 1 2 F SS Cool 1 2 F 1 7 F 5 Select Compressor Lockout CL OFF or ON Selecting CL On will cause the thermostat to wait 5 minutes between cooling cycles This is inten...

Страница 6: ...ate 3 Press to adjust temperature setting below room temperature The heating system should stop operating To prevent compressor and or property damage if the outdoor temperature is below 50o F DO NOT operate the cooling system CAUTION Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes...

Страница 7: ... to thermostat or system 3 Cooling System requires service or thermostat requires replacement Set System Switch to Cool and lower setpoint below room temperature Verify thermostat and system wires are securely at tached Same procedures as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room temperature There may be up to a five minute delay befor...

Страница 8: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Страница 9: ...ite rodgers com White Rodgers es una división de Emerson Electric Co El logotipo de Emerson es una marca comercial y una marca de servicio de Emerson Electric Co Línea de ayuda para el usuario 1 800 284 2925 ...

Страница 10: ...calefacción esté funcionando correctamente El sistema no enfría 1 El interruptor System no está ajustado en Cool 2 La conexión al termostato o al sistema está suelta 3 El sistema de enfriamiento requiere servicio técnico o debe cambiarse el termostato Ajuste el interruptor System en Cool y baje la temperatura de referencia por debajo de la temperatura ambiente Verifique que los cables del termosta...

Страница 11: ...e la temperatura por debajo de la temperatura ambiente El sistema de calefacción debería dejar de funcionar Para evitar daños al compresor y o daños materiales si la temperatura externa está por debajo de los 50 F NO utilice el sistema de enfriamiento PRECAUCIÓN No deje que el compresor funcione a menos que los calentadores de aceite del compresor hayan estado en funcionamiento durante 6 horas y q...

Страница 12: ... FA Para cambiar la velocidad del ciclo presione el botón y el botón Las velocidades de los ciclos son las indicadas a continua c ión según la opción elegida MODO Rápido Medio Lento FA ME SL SS Heat 0 6 F 0 8 F 1 2 F SS Cool 1 2 F 1 7 F 5 Selección de bloqueo del compresor CL en OFF u ON Si se selecciona CL On el termostato esperará 5 minutos entre ciclos de enfriamiento para evitar que el compres...

Страница 13: ...talla botones e interruptores del termostato SYSTEM 2 1 3 4 5 6 7 8 9 11 10 8 Muestra la temperatura actual 9 Service servicio indica una falla en el sistema de calefacción enfriamiento No indica una falla del termostato 10 Change Filter cambiar filtro aparece cuando el sistema se ha utilizado por la cantidad de tiempo seleccionada en el filtro para recordarle que debe cambiar o limpiar el filtro ...

Страница 14: ... en uno de los sistemas retire el transformador del sistema SIN circuitos de seguridad NOTA Puente opcional para bomba de calor de una sola etapa R C G W Y O B 24 VCA 120 VCA VIVO NEUTRO VIVO NEUTRO NEUTRO NEUTRO Figura 4 Diagrama de conexiones típico para sistemas de una sola etapa de dos transformadores con circuitos de seguridad en AMBOS sistemas Relé de conmutación Contactor del compresor Relé...

Страница 15: ...tato viene ajustado de fábrica en la posición O Esta opción admite la mayoría de las aplicaciones de bomba de calor que requieren que el relé de conmutación esté energizado en COOL Si el termostato que está cambiando o la bomba de calor que está instalando con este termostato requiere una terminal B para energizar el relé de conmutación en HEAT el interruptor O B debe colocarse en la posición B Or...

Страница 16: ...e programación 1F86 0244 No Programable ESPECIFICACIONES Características eléctricas Alimentación con pilas mV a 30 VCA 50 60 Hz o CC Entrada Cableado interno 20 a 30 VCA Carga en terminales 1 0 A por terminal 1 5 A máx en todas las terminales combinadas Rango de temperatura de referencia 45 a 90 F 7 a 32 C Diferencial una sola etapa Calor 0 6 F frío 1 2 F ajustable Diferencial bomba de calor Calor...

Отзывы: