background image

Printed in U.S.A.

8/08

©

 

Copyright 2008 TAC All Rights Reserved.

F-24576-4

Application

The 2212-318 and 2212-319 Dual Setpoint/Deadband 
Pneumatic Room Thermostats are designed for the 
proportional control of pneumatic valves, damper 
actuators, or other final control devices in 
environmental control systems. These devices are 
used when it is desirable to set up, between selected 
heating and cooling setpoints, a temperature span 
within which the HVAC system uses no energy for 
heating or cooling. The high capacity, two-pipe, 
pilot-operated, relay-type design provides pneumatic 
feedback for accuracy and stability over the entire 
operating range.

These thermostats are available in either direct- or 
reverse-acting models, each utilizing two bimetals, one 
heating and one cooling, to interrupt the deadband 
(branch) pressure. In the direct-acting model, the 
heating bimetal modulates the pressure between zero 
and the deadband pressure, and the cooling bimetal 
modulates the branch pressure between the deadband 
pressure and main air pressure. In the reverse-acting 
model, this action is reversed. The deadband pressure 
is adjustable in the field, to adapt to specific 
applications. Two concealed setpoint dials, one 
heating and one cooling, are used to set the individual 
heating and cooling setpoints to the desired values. 
This creates the desired deadband between the two 
selected setpoints. All calibration functions are 
accessible from the front of the thermostat. The use of 
a blank cover (21-928) is recommended with this 
device. Other cover options may be utilized if desired.

Features

Factory-calibrated, stainless steel ball-in-seat 
provides pneumatic feedback for stable, linear 
operation.

Deadband is easily selected by setting the desired 
heating and cooling setpoints.

Field-adjustable deadband output pressure is 
factory set at 8 psig.

Leak-proof, self-closing branch gauge tap.

SPECIFICATIONS

Action: Proportional.
Setpoint Range:

Heating, 57 to 75

°

F (14 to 24

°

C).

Cooling, 65 to 83

°

F (18 to 28

°

C).

Throttling Range: 1.5

°

F (approx.) non-adjustable for each 

setpoint.
Maximum Air Pressure: 30 psig.
Main Air Consumption: 30 scim.
Setpoint Adjustment: Individual concealed adjustments for 
heating and cooling by means of a 20-881 calibration wrench.
Calibration:

Deadband, Factory-set at 8 psig (adjustable).
Direct-Acting Models,

Heating 5.5 psig at setpoint.
Cooling 10.5 psig at setpoint.

Reverse-Acting Models,

Cooling 5.5 psig at setpoint.
Heating 10.5 psig at setpoint.

Construction:

Mechanical Components, Die cast aluminum, stainless 
steel, and glass-filled nylon.
Diaphragm, Fabric-reinforced Neoprene.
Air Lines, Connect to thermostat nipples with 
spring-reinforced plastic tubes.
Branch Connections, Equipped with internal fiters.

Environment

Humidity: 5 to 95% relative humidity, non-condensing.
Locations: NEMA Type 1.

2212-318
2212-319

Dual Setpoint/Deadband

Pneumatic Room Thermostats

General Instructions

Blank Cover Shown
(Covers must be ordered 
separately except as noted.)

Summary of Contents for 2212-318

Page 1: ...setpoints All calibration functions are accessible from the front of the thermostat The use of a blank cover 21 928 is recommended with this device Other cover options may be utilized if desired Feat...

Page 2: ...nal 22 1057 C11 48 Euro white Plastic 21 960 C14 42 Satin Chrome Metal Blank Concealed Yes Internal 22 1060 C14 48 Euro white Plastic Table 4 Accessories Wholesale Number Replaces Model Description 20...

Page 3: ...the applicable figure Figure 2 through Figure 8 See Figure 12 for mounting dimensions Branch Main Polyethylene Tubing Air Supply 20 714 Wall Plate included with thermostat 21 473 Drywall Mounting ord...

Page 4: ...it 2 Optionally the thermostat may be mounted with the 6 x 1 in self tapping screws provided in the 22 023 kit 3 Use the 8 x 1 in mounting screws provided in the 22 023 kit when mounting the wall plat...

Page 5: ...hole Figure 10 or Figure 11 2 Be sure ambient temperature is between 65 and 75 F Turn the heating dial to 57 F and the cooling dial to 83 F 3 Adjust the deadband pressure by turning calibrating screw...

Page 6: ...cting models refer to Figure 11 and proceed with calibration as outlined under the procedures for the direct acting models Note If for some reason a thermostat gets completely out of adjustment and do...

Page 7: ...ar maintenance of the total system is recommended to assure sustained optimum performance FIELD REPAIR None Replace an inoperative thermostat with a functional unit DIMENSIONAL DATA 1 1 4 3 18 1 3 8 3...

Page 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 24576 4 TAC 1354 Clifford Avenue P O Box 29...