Single flow pulse
Set the single flow pulse, that is, how much
accumulated flow is represented by each rising edge
pulse output;
Note: The pulse period is at least 200ms, that is, a
maximum of 5 pulses are output per second. Therefore,
the value needs to be adjusted according to the actual
situation. For example, if the set value is 1.20, then
the instantaneous value must not exceed 5*1.2=6, that
is, it must not exceed 6 units per second. Cumulative
unit can be changed in MENU 32.
This setting is related to OCT, select 1. NET Int Pulse
toutput cumulative pulse in MENU 78.
This setting is related to the relay, select 3.NET Int
Pulse output cumulative pulse in MENU 79.
Current Loop Mode Select
0.
4-20mA
set up the 4-20mA output to. be flow rate mode
1.
4-20mA vs.Vel.
set up the 4-20mA output to. be velocity mode
Other different current output characteristics are displayed in below figures. The user can select one of them
according to his actual requirements.
In two graphs shown above, flow F
4mA
indicates the value that the user entered in Window M56; and flow F
20mA
indicates the value that the user entered in Window M57.
Menu
5
3
Single Pulse Flow
1.20 m3
Menu
5
5
CL Mode Select [55
0. 4 -
20 mA