Servicing and Upgrading a CX200-Series DPE2
Replacing a Power Supply/System Cooling Module
This section explains how to replace a power supply/system cooling
module, and a CX200LC blower module.
CAUTION
!
Handle the modules gently and use an ESD wristband. Do not
remove a power/cooling or blower module until you have a
replacement module available.
If one power supply is off and the other is on, do not turn one on
and immediately turn off the other. Instead, turn one on and wait
five seconds after the green LED lights before turning the other off.
Turn off the power supply before unplugging the power cord from
a module or cabinet power strip.
Removing a Power
Supply/System
Cooling Module
Access to the disks in your enclosure will time out two minutes after
you remove a power supply/system cooling module or a blower
module from the system. While the system can continue operating on
a single power supply, the loss of a module’s two blowers will cause a
time-out unless you replace the module within two minutes.
Follow these steps to replace a power supply/system cooling module
or a blower module.
1. If you are replacing a power/cooling module, turn off the power
supply and unplug its ac line cord. Figure 3-13 shows the power
switch and line cord location on a CX200.
Содержание CX200-Series
Страница 4: ...EMC CX200 Series DPE2 Hardware Reference iv ...
Страница 42: ...2 18 EMC CX200 Series DPE2 Hardware Reference Installing a CX200 Series DPE2 ...
Страница 64: ...3 22 EMC CX200 Series DPE2 Hardware Reference Servicing and Upgrading a CX200 Series DPE2 ...
Страница 80: ...A 12 EMC CX200 Series DPE2 Hardware Reference Technical Specifications and Operating Limits ...
Страница 86: ...g 6 EMC CX200 Series DPE2 Hardware Reference Glossary ...