www.eltherm.com
20
operation manual
temperature contoller ELTC-MV2
BU 123
Revision 1
Ramp mode with continuous output
The actual value x is recorded via a temperature sensor or a
standard signal and converted into a digital signal. Before this
signal is sent to the controller, the actual value is corrected.
The corrected actual value is shown on the display.
The setpoints w1 to w9 and the associated running times t1
to t9 are set on the controller. The current ramp phase, the
current setpoint and the remaining run time of the ramp
section can be shown on the display.
The size of the output signal can be limited by a minimum
and maximum value on the controller.
The hysteresis h is set on the controller. When controlling with
a continuous output, the hysteresis indicates the range in
which the output signal varies between 0/4mA and 20mA or
0/2V and 10V.
The control difference x
di
= w
i
- x is formed with the current
setpoint in the controller.
If the control difference is x
di
< h, he output emits a signal up
to 20mA or 10V.
If the control difference is x
di
≥ h, he output emits a signal of
20mA or 10V.
If the actual value is above the set setpoint w, the output
emits a signal of 0/4mA or 0/2V.
Parameters used
No. description
factory
setting
Own
setting
P10 control setpoint 1 (= W1)
5
P11 switching hysteresis 1
2
P15 sensor correction 1
0
P16 over temperature alarm 1
999
P17 low temperature alarm 1
-99
P18 Lower analog scaling value
0
P19 Upper analog scaling value
100
P28
power monitoring
load output
0
P50 start value
100
P51 Ramp 1 duration
30
P52 Ramp 1 setpoint
100
P53 Ramp 2 duration
30
P54 Ramp 2 setpoint
100
P55 Ramp 3 duration
30
P56 Ramp 3 setpoint
100
P57 Ramp 4 duration
30
P58 Ramp 4 setpoint
100
P59 Ramp 5 duration
30
P60 Ramp 5 setpoint
100
P61 Ramp 6 duration
30
P62 Ramp 6 setpoint
100
P63 Ramp 7 duration
30
P64 Ramp 7 setpoint
100
P65 Ramp 8 duration
30
P66 Ramp 8 setpoint
100
P67 Ramp 9 duration
30
P68 Ramp 9 setpoint
100
P69 band alarm hysteresis
5
P75
Low Level mode analog inputs/
outputs
0
P76
min. output signal analogue
output
0
P77
max. output signal analogue
output
100
Structure switch settings
No.
description
selection option
S01
Selection actual
value X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03
Select setpoint W
3 = ramp function
S04
Selection of output
function controller
4 = continuous control
S05
Selection swit-
ching output
3 = analog output clocked
Parameters used
No. description
factory
setting
Own
setting
P01 input variable 1 (X1)
Display only
P03 reference variable (W)
Display only
P04 current display
Display only
P07 current ramp phase
Display only
P08 remaining time ramp phase
Nur Anzeige