background image

www.eltherm.com

12 

operation manual

temperature contoller ELTC-MV2

BU 123

Revision 1

SETPOINT CONTROLLER (W1)

Setpoint  controller  (W1)  2-point

The actual value x is recorded via a temperature sensor or a  
standard signal and converted into a digital signal. Before this  
signal is sent to the controller, the actual value is corrected.  
The corrected actual value is shown on the display.
The setpoint w is set on the controller and shown on the 
display.
A hysteresis h can be set on the controller. 
The control difference x

d

 = (w - h) -x  is formed in the control-

ler.

Hybrid relay K1 (2-point)

If the control difference is x

d

 < 0 , the hybrid relay opens.

If the control difference is x

≥ 0 , the hybrid relay closes.

Control of an external SSR relay (2-point)

The external SSR relay is switched via a voltage signal from the 
controller.

If the control difference is x

d

 < 0 , a 0/2V signal is sent to the 

output and the SSR relay switches off.
If the control difference is x

≥ 0 , a 10V signal is given to the 

output and the SSR relay switches on.

Control of an external power contactor (2-point)

The external power contactor is switched via the controller's 
safety relay.
A hysteresis h can be set on the controller.

If the control difference is x

d

 < 0 , the safety relay opens and 

the external power contactor switches off.
If the control difference is x

≥ 0 , the safety relay closes and 

the external power contactor switches on.

Structure switch settings

No.

description

selection option

S01

Selection actual 
value X1

[1] = Pt100, 3-wire (AE1) 
2 = Pt100, 2-wire (AE1) 
3 = thermocouple type J (AE1)  
4 = thermocouple type K (AE1)  
5 = voltage input (AE3) 
6 = current input (AE3)

S03

Select setpoint W

[1] = Fixed value W1

S04

Selection of output 
function controller

[1] = two-point control

S05

Selection swit-
ching output

[1] = internal hybrid relay with 
soft start 
2 = external power contactor 
3 = analog output clocked

Parameters used

No.

description

factory set-

ting

Own 
setting

P01 Input variable X1

Display only

P03 Reference variable W

Display only

P04 Current display

Display only

P10 Control setpoint 1 (=W1)

5

P11 Switching hysteresis

2

P12 min. standstill time K1

0

P13

largest adjustable setpo-
int 1

950

P14

smallest adjustable 
setpoint 1

-50

P15 sensor correction 1

0

P16

Over temperature alarm 1

999

P17 low temperature alarm 1

-99

P18

Lower analog scaling  
value

0

P19

Upper analog scaling  
value

100

P28

power monitoring 
load output

0

P75

Low level mode analog 
inputs/outputs

0

FUNCTIONAL DESCRIPTIONS

Содержание ELTC-MV2

Страница 1: ...ERATION MANUAL ELTC MV2 Handling operation and adjustment ELTC MV2 Moduvise eltherm GmbH Ernst Heinkel Straße 6 10 57299 Burbach Germany T 49 2736 4413 0 F 49 2736 4413 0 info eltherm com BU 123 P 1 2 3 4 www eltherm com ...

Страница 2: ...GER indicates an extremely dangerous situation If it is not avoided there is a danger to life or at least a high risk of serious injury 3 3 3 4 5 5 5 5 5 5 DESCRIPTION AND TECHNICAL DATA DESCRIPTION TECHNICAL SPECIFICATIONS CONNECTION AND CONTROL PANEL SPECIAL CONDITIONS INSTALLATION AND SAFETY INSTRUCTIONS GOODS RECEIPT STORAGE DISPOSAL DECLARATION OF CONFORMITY 6 6 7 7 10 11 12 12 16 21 24 27 27...

Страница 3: ...external release of the load output DigIn2 is used with the structure switch position S04 5 limiter function and serves as an external unlocking DigIn3 is used with structure switch position S03 6 W1 W2 switchover and is used to switch between W1 and W2 Dimensions ELTC MV2 TECHNICAL SPECIFICATIONS contoller type ELTC MV2 operating voltage 100V 277VAC 10 50 60Hz 24VDC 5 power consumption max 5 5 W ...

Страница 4: ... 2 GND U I SCADA ModBus 12V S GND A B System ModBus GND A B Input external U I 1 I GND U Input U I I GND U Sensor 2 Sensor 1 X10 X9 X8 X7 X6 X5 X4 X3 X2 X1 2 1 4 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 3 2 1 5 4 3 2 1 X11 X12 X13 X14 X15 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 N Terminal N N N PE Terminal PE PE PE Power supply input A heating cable output L A L1 L1 L heca Alarm relay Com NC NO OT Relay ...

Страница 5: ...aid parallel to lines carrying mains voltage The total line resistance must not exceed 10 ohms After switching on the controller the display shows the current actual value NOTE Storage should be in a dry place at an ambient temperature of 0 C to 50 C NOTE The WEEE logo shown above indicates that this product should not be disposed of with your household waste You can obtain more information on dis...

Страница 6: ...P01 or T 1 minute Exit input mode Call up and change structure switches In order to reach the structure switch list the and keys must be pressed simultaneously in the parameter list for approx 3 seconds until S01 appears on the display Press P for 3 seconds Parameter no appears Press and simultaneously for 3 seconds Structure switch S01 appears Press Select structure switch Press P switch position...

Страница 7: ...d down in a controlled man ner rF2 band alarm occurred during operation rF3 ramp aborted The ramp status is indicated by a flashing display alternating with parameter P01 3 seconds P01 1 second rFx You can return to the normal display by pressing the P key PARAMETERS AND THEIR MEANING The factory settings are specified in Parameter meaning and range P01 Input variable X1 Display only resolution C ...

Страница 8: ...edium selection Range 1 5 2 see table on page 10 P46 Geometry 0 pipe 1 container P47 Metal pipe outer diameter Range 1 32 11 see table on page 10 P48 Plastic pipe outer diameter Range 1 17 3 see table on page 10 Parameter meaning and range P49 Cooling times 0 calculated by para meters P41 P48 1 TU 30 seconds 2 TU 60 seconds 3 TU 120 seconds P50 Start value setpoint ramp Range noP 1 950 C 100 C P51...

Страница 9: ...2 mm 40 83 mm 11 12 7 mm 1 2 41 89 mm 3 1 2 12 13 mm 42 90 mm 13 14 mm 43 95 mm 3 3 4 14 14 3 mm 9 16 44 100 mm 4 15 15 mm 3 5 45 110 mm 16 16 mm 5 8 46 114 mm 4 1 2 17 17 mm 47 120 mm 18 17 5 mm 11 16 48 127 mm 5 19 18 mm 49 130 mm 20 19 mm 3 4 50 140 mm 5 1 2 21 20 mm 51 150 mm 22 23 32 mm 4 5 52 153 mm 6 23 22 mm 7 8 53 160 mm 24 24 mm 15 16 54 165 mm 6 1 2 25 25 mm 1 55 170 mm 26 30 mm 56 178 ...

Страница 10: ... 13 150 mm 6 5 25 mm 1 14 200 mm 8 6 32 mm 1 1 4 15 250 mm 10 7 40 mm 1 1 2 16 300 mm 12 8 50 mm 2 17 400 mm 16 9 65 mm 2 1 2 no meaning S01 Selection actual value X1 1 Pt100 3 wire AE1 2 Pt100 2 wire AE1 3 Thermocouple type J AE1 4 Thermocouple type K AE1 5 Voltage input AE3 6 Current input AE3 S02 Selection actual value X2 0 Input disabled 1 Pt100 3 wire AE2 2 Pt100 2 wire AE2 3 Thermocouple typ...

Страница 11: ...t In 3 Alarm X1 High temp Bit 9 Bit 10 Bit 11 Alarm X1 Low temp Alarm X2 High temp Alarm X2 Low temp Bit 12 Bit 13 Bit 14 Alarm Heating cable Bit 15 Bit 16 Bit 17 State X1 Pre High temp State X1 Pre Low temp Bit 18 Bit 19 Bit 20 State X2 Pre High temp State X2 Pre Low temp State External off mode Bit 21 Bit 22 Bit 23 State External SP2 mode Bit 24 Bit 25 Bit 26 E01 AE1 short E02 AE1 open E03 AE1 3...

Страница 12: ...ntroller s safety relay A hysteresis h can be set on the controller If the control difference is xd 0 the safety relay opens and the external power contactor switches off If the control difference is xd 0 the safety relay closes and the external power contactor switches on Structure switch settings No description selection option S01 Selection actual value X1 1 Pt100 3 wire AE1 2 Pt100 2 wire AE1 ...

Страница 13: ...n external power contactor PWM The external power contactor is switched via the controller s safety relay If the control difference is xd h the safety relay clocks If the control difference is xd h the safety relay remains permanently closed If the control difference is xd 0 the safety relay remains open Structure switch settings No description selection option S01 Selection actual value X1 1 Pt10...

Страница 14: ...mum ambient temperature the load contact is closed Control of an external SSR relay proportional control The external SSR relay is switched via a voltage signal from the controller If the ambient temperature is above the set setpoint P10 the analogue output emits a signal of 0 2V At ambient temperature below the entered minimum ambient temperature P41 1 6 of the difference between the setpoint mai...

Страница 15: ...emits a signal of 0 4mA or 0 2V Structure switch settings No description selection option S01 Selection actual value X1 1 Pt100 3 wire AE1 2 Pt100 2 wire AE1 3 thermocouple type J AE1 4 thermocouple type K AE1 5 voltage input AE3 6 current input AE3 S03 Select setpoint W 1 Fixed value W1 S04 Selection of output function controller 4 continuous control S05 Selection swit ching output 3 analog outpu...

Страница 16: ...permanently Cancel ram immediately Press button and simultaneously for 5 seconds LED 2 flashes alternately long short Press button and simultaneously again for 5 seconds LED 2 goes out The ramp function is now inactive the set temperature setpo int P10 is then approached and maintained permanently Ramp mode 2 point The actual value x is recorded via a temperature sensor or a standard signal and co...

Страница 17: ...n Parameters used No description factory setting Own setting P01 input variable 1 X1 Display only P03 reference variable W Display only P04 current display Display only P07 current ramp phase Display only P08 remaining time ramp phase Display only P10 control setpoint 1 W1 5 P11 switching hysteresis 1 2 P15 sensor correction 1 0 P16 over temperature alarm 1 999 P17 low temperature alarm 1 99 P18 L...

Страница 18: ...setpoint 100 P53 Ramp 2 duration 30 P54 Ramp 2 setpoint 100 P55 Ramp 3 duration 30 P56 Ramp 3 setpoint 100 P57 Ramp 4 duration 30 P58 Ramp 4 setpoint 100 P59 Ramp 5 duration 30 P60 Ramp 5 setpoint 100 P61 Ramp 6 duration 30 P62 Ramp 6 setpoint 100 P63 Ramp 7 duration 30 P64 Ramp 7 setpoint 100 P65 Ramp 8 duration 30 P66 Ramp 8 setpoint 100 P67 Ramp 9 duration 30 P68 Ramp 9 setpoint 100 P69 band al...

Страница 19: ...difference is xdi h the analogue output and the SSR relay clocks If the control difference is xdi h a 10V signal is sent to the output and the SSR relay switches on If the control difference is xdi 0 a signal with 0 2V is sent to the output and the SSR relay switches off Control of an external power contactor PWM The external power contactor is switched via the controller s safety relay If the con...

Страница 20: ...setpoint 1 W1 5 P11 switching hysteresis 1 2 P15 sensor correction 1 0 P16 over temperature alarm 1 999 P17 low temperature alarm 1 99 P18 Lower analog scaling value 0 P19 Upper analog scaling value 100 P28 power monitoring load output 0 P50 start value 100 P51 Ramp 1 duration 30 P52 Ramp 1 setpoint 100 P53 Ramp 2 duration 30 P54 Ramp 2 setpoint 100 P55 Ramp 3 duration 30 P56 Ramp 3 setpoint 100 P...

Страница 21: ...ernal SSR relay is switched via a voltage signal from the controller If the control difference is xd 0 a 0 2V signal is sent to the output and the SSR relay switches off If the control difference is xd 0 a 10V signal is given to the output and the SSR relay switches on Control of an external power contactor 2 point The external power contactor is switched via the controller s safety relay If the c...

Страница 22: ...intaining temperature and the minimum ambient temperature the load contact is closed At ambient termperatures in between the controller runs in cycle mode The output level P05 is used as the basic display Control of an external SSR relay proportional control The external SSR relay is switched via a voltage signal from the controller The load contact is open at ambient temperatures above the setpoi...

Страница 23: ... hysteresis 2 P12 min standstill time K1 0 P15 sensor correction 1 0 P16 Over temperature alarm 1 999 P17 low temperature alarm 1 99 P18 Lower analog scaling value 0 2V 0 4mA 0 P19 Upper analog scaling value 10V 20mA 100 P28 power monitoring load output 0 P75 Low Level mode analog inputs outputs 0 P76 min output signal analogue output 0 P77 max output signal analogue output 100 External setpoint w...

Страница 24: ... the control difference is xd 0 a 0 2V signal is sent to the output and the SSR relay switches off If the control difference is xd 0 a 10V signal is given to the output and the SSR relay switches on Ansteuerung eines externen Leistungsschützes 2 Punkt If the control difference is xd 0 the safety relay opens and the external power contactor switches off If the control difference is xd 0 the safety ...

Страница 25: ...outputs 0 Hybrid relay K1 PWM If the control difference is xd h the hybrid relay clocks If the control difference is xd h he hybrid relay remains permanently closed If the control difference is xd 0 the hybrid relay remains open ontrol of an external SSR relay PWM The external SSR relay is switched via a voltage signal from the controller If the control difference is xd 0 a signal with 0 2V is sen...

Страница 26: ... the actual value is above the set setpoint w the output emits a signal with 0 4mA or 0 2V Structure switch settings No description selection option S01 Selection actual value 1 X1 1 Pt100 3 wire AE1 2 Pt100 2 wire AE1 3 thermocouple type J AE1 4 thermocouple type K AE1 5 voltage input AE3 6 current input AE3 S02 Selection actual value 2 X2 1 Pt100 3 wire AE2 2 Pt100 2 wire AE2 3 thermocouple type...

Страница 27: ...2 Pt100 2 wire AE1 3 thermocouple type J AE1 4 thermocouple type K AE1 5 voltage input AE3 6 current input AE3 S03 Select setpoint W 1 fixed value W1 S04 Selection of output function controller 5 limiter S06 Alarm temperature absolute relative 1 absolute 2 relative S07 Select controller release DigIn1 1 continuously 2 external Parameters used No description factory setting Own setting P01 Input va...

Страница 28: ...eltherm GmbH Headquarters Ernst Heinkel Straße 6 10 57299 Burbach Germany T 49 2736 4413 0 F 49 2736 4413 50 info eltherm com www eltherm com 8642050611135 Betriebsanleitung ELTC MV2 EN ...

Отзывы: