Quick Start Guide
Minipack PS System
356808.103, 1v2-2008-10
23
System Interface Card ~ Terminals & Pin-out
Minipack
systems are shipped from factory with the CON5 signals already connected.
Some of the
Smartpack
controller’s internal system signals are accessible on D-Sub connector
CON5, on the controller’s rear panel.
Using a standard 15 pins D-Sub cable, the signals on CON5 are routed to the
Minipack
system’s
main circuit board. See the figure in this section for an overview of the signals on CON5,
LVD Latching Contactors
Connections
Minipack
systems’ LVBD and LVLD functionality (Low Voltage Battery Disconnect; LV Load
Disconnect) is implemented by the
Smartpack
controlling magnetically latching contactors.
The coil of latching contactors is not energized in any state. They change state from open to close,
or vice versa, when a reversed pulse is applied to the coil.
System
Connections
CON5
15 pins D-Sub (female)
LVD1A +/
−
1
LVD2A +/
−
2
LVD /
−
3
System Voltage
+
4
System Voltage
−
5
a
*Batt Current 1
+
6
b
*Batt Current 1
−
7
NC
8
Load Fuse Fail 1
+
9
Power Input
+
10
Load Fuse Fail 1
−
11
c
*Batt Fuse Fail 1
+
12
d
*Batt Fuse Fail 1
−
13
System Reference
14
Power Input
−
15
FUNCTION
SIGNALPIN-OUT
5 1
15 11
CON5
(female; orange)
Smartpack
controller
Latching Contactors, LVD1 & LVD2
Correct Use of Latching Contactors (example)
A latching contactor changes state only when a
reversed pulse voltage is applied to its coil
+ Pulse
ON
- Pulse
OFF
10
8
9
X:*****
+
—
LVD1A
LVD2A
LVD Common
Smartpack
controller
Minipack PS System
(internal)
11
LVD Common
Latching
Contactor
LVD2
Y
X
Latching
Contactor
LVD1
Y
X
Minipack
Main PCB
Internal Connections
Appendix
Latching Contactor B
Latching Contactor A
Bidirectional
diode
Warning!
The
bidirectional
diode must
always be
mounted to
avoid dam-
aging the
controller.
Y
X
Y
X
Two Types of Latching Contactors
Содержание Minipack
Страница 17: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 20: ......
Страница 22: ...PULLOUT...
Страница 24: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...
Страница 35: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 27...
Страница 36: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 28...
Страница 39: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 31...