External AC Fuses 

 Recommended Rating 

The site’s AC supply quality is of great importance. In general, a site with better AC supply quality 
(stable nominal voltage) may use smaller breakers. 

 

 

 

 

 

 

 

 

 

 

 

 

CAREFUL:

  

Minipack systems using 48V-400W rectifiers may also use the recommended external breakers specified in the 800W 
Rectifiers table above, even though smaller breakers could be employed.  
For more information, read document 2028364 

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING:

  

Always replace a rectifier with blown internal AC fuse with a new module, and send the malfunctioning module for servicing. 

 

WARNING:

  

You must always consider re-dimensioning the external AC fuses and AC cabling, before swapping 400W, 800W or 
800W WIR Minipack rectifiers in the same Minipack system. 

 

AC Mains

 Appendix 

AC Mains 

No of

Current Max.

Ext. Fuse

Input Type 

Rectifiers

per input (A)

205VAC

185VAC

Type

205VAC

185VAC

 

N

3 phase (Y)

I

4

8.77

{ 9.72} 10A-D/16A-C {

equal} 

II

6

(equal row I)

(equal row I) 

230VAC 

3 phase (

Δ

)

III

4

15.2

{ 16.8}

16A-C

{20A-C} 

IV

6

(equal row III)

(equal row III) 

230VAC 

1 phase 

V

4

17.5

{ 19.4}

20A-C

{

equal} 

VI

6

26.3

{ 29.5}

32A-C

{

equal} 

Doc 2024398,1v0 

Notes: 

  Use the values in {} brackets in the 185VAC column, if you are 

unsure or know that the available AC mains voltage may drop 

below 205VAC. 

  Each phase feeds two 800W rectifiers 

  The recommendations apply for use of Thermal magnetic circuit 

breaker, type Siemens 5SX or 5SY series, MG C60H series or 

similar. For more information regarding External AC fuses and 

other types of fuses, please read the document 2024398. 

Recommended External AC Fuses per AC Mains Feed Input 

Minipack Systems with 48 VDC 800W Rectifiers 

AC Mains 

No of

Current Max.

Ext. Fuse 

Input Type 

Rectifier

per input (A)

230VAC

150VAC

100VAC

Type 

230VAC

150VAC 100VAC

 

3 phase (Y) 

I 4

7.73

{ 7.73}

[14.22]

25A-C {

equal}  [

equal] 

II 6

(equal row I)

(equal row I) 

230VAC 

3 phase (

Δ

III 4

(equal row I)

(equal row I) 

IV 6

(equal row I)

(equal row I) 

230VAC 

1 phase 

V 2

7.73

{ 11.9}

[14.3]

(equal row I) 

VI 4

15.5

{ 23.7}

[28.5]

25A-C {32A-C} 

[32A-C] 

VII 6

23.2

{ 35.6}

[42.7]

32A-C {40A-C} [50A-C] 

Doc 2043538,1v0 

Notes: 

  Use the values in {} brackets in the 150VAC column, if you are unsure or know that the 

available AC mains voltage may drop between 230VAC and 150VAC, or use the 

values in [] brackets in the 100VAC column if the voltage may drop below 150VAC. 

  Each phase feeds two 800W WIR rectifiers (Wide Input Range) 

  The recommendations apply for following air breaker types:  

- Up to 32A, use Melnrining DBN32 C char series or similar  

- Bigger than 32A, use Melnrining DB47-63A C char series or similar.  

For more information regarding External AC fuses and other types of fuses, please 

read the document 2043538. 

Recommended External AC Fuses per AC Mains Feed Input 

Minipack Systems with 48 VDC 800W WIR Rectifiers 

Содержание Minipack

Страница 1: ...arm Interface Card Terminals Pin out 21 o Alarm Interface Card Extended Terminals Pin out 22 o Alarm Interface Card External Terminals Pin out 22 Internal Connections o System Interface Card Terminals...

Страница 2: ...and use three phase rectifier modules Minipack systems are suitable as small stand alone battery chargers and DC power supplies Brief System Description Minipack The Minipack PS system is a compact an...

Страница 3: ...iver to loosen the locking screw 2 Insert or remove the module by sliding it on its mounting rail fully into the power shelf so that the module makes proper contact hot pluggable or using the front ha...

Страница 4: ...r locking screws on both left and right side plates The drawer is then securely locked in the shelf in its Operation Position Minipack blind cover Locking screw to secure the blind cover Front handle...

Страница 5: ...ing or Mounting Load MCBs CAUTION Power must be OFF during this operation 1 Remove the F1 F2 plastic cover by unscrewing the cover s frontal screw then inserting a small screwdriver into the cover s g...

Страница 6: ...echanical Installation Power is OFF Carry out the following CAUTION When transporting cabinetized Minipack systems with mounted rectifier modules ensure that support plates or structures are always mo...

Страница 7: ...Output Rail is connected to Telecom Earth TE at only one place at the cabinet cable X7A or at a central distribution point o For each DC load connect one of the cables to the common DC output termina...

Страница 8: ...ack controller X6A Common DC Output Load terminal block DC Output Load terminal block Cable Fastening Plate X5 pin 1 X6B pin 1 LVLD latching contactor optional LVBD latching contactor Minipack 6 Recti...

Страница 9: ...ifiers have 10 DC load outputs Common Battery Rail Battery Fuses Fb1 Fbx Battery Cables string 1 Battery Cables string x M6 screws cable lugs max 15 mm width X7A Interface Cards Connections Refer to t...

Страница 10: ...the AC input cable s and external AC fuses are sized and rated as specified o Check that AC Earth PE is terminated and electrically connected to chassis 4 Site specific parameters and settings are kn...

Страница 11: ...rtunity to enter site related information number of used AC phases type of batteries etc Load Adjustments Power is ON Now you can begin with stage III where you will adjust again the output voltage to...

Страница 12: ...Test Int Guard Time Start Stop Test RemoveUnit s Rem Reset 3v03 Rectifier ON OFF 3v03 Rectifier Setup System ON OFF 3v03 RectWalkInTime Short Long 3v03 Enable Disable Charge Curr Lim MainsFeed 3v03 Ge...

Страница 13: ...ws to install USB drivers Follow accept the wizard default steps to automatically install the USB drivers the wizard runs twice 4 Start PowerSuite and establish connection Select Start All Programs El...

Страница 14: ...controllers 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 ID Smartnodes 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ID Battery Monitor CAN nodes 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 ID Load Mo...

Страница 15: ...5VAC Each phase feeds two 800W rectifiers The recommendations apply for use of Thermal magnetic circuit breaker type Siemens 5SX or 5SY series MG C60H series or similar For more information regarding...

Страница 16: ...shelf To achieve a more controlled ID assignment you should always insert hot plug new Minipack rectifiers in the power shelf one module at a time in following shelf position order 1 3 5 and 2 4 6 Th...

Страница 17: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...

Страница 18: ...Unlock the upper and lower screws and slide the drawer shelf open then lift the Melenex plastic cover Electrical Installation Power is OFF CARRY OUT FOLLOWING OK 9 Make the system completely voltage f...

Страница 19: ...Fb4 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 LOAD BATT Form 175 gb v1 C01_356808 103_qstart inst comm oper_minipack pss_1v2 docx_mfm_2006 12 29 www eltekvalere com Headquarters Eltek Valere 1303 E Arapaho Rd Ri...

Страница 20: ......

Страница 21: ...ocations in the power shelves 5 The Smartpack and all rectifier modules are working LEDs are ON Verify 6 Connect a PC to the PS system Install the PowerSuite software if required 7 DC output voltage M...

Страница 22: ...PULLOUT...

Страница 23: ...Suite PC application to check all rectifiers output the same amount of current 1A 9 Display the stored log of Alarm Messages Using the keypad on the Smartpack controller or from the PC System Adjustme...

Страница 24: ...PULLOUT Check Lists Pullout Pull out the pages with the gray outer band and use them as check lists...

Страница 25: ...Block Battery String and Battery Bank 48V Battery Bank Battery String 1 48V Batt Battery Block 12V Battery String 2 48V Notice that if you open the serial switches in card Art 200576 setting all to O...

Страница 26: ...ect Battery Monitor with ID 33 to battery string 1 lowest with ID 34 to string 2 and so on PowerSuite will then refer to the correct battery string Four measurements per string 48V Outer Terminal Bloc...

Страница 27: ...re not shipped with the Battery Monitor Symmetry Kit Battery Monitoring Appendix Battery Symmetry String 1 to 4 Mid point Measurement One measurement per string four strings Battery Monitor Part 24210...

Страница 28: ...8 7 6 10 14 13 12 11 X4 Batt Symmetry 1 Batt Symmetry 2 Batt Symmetry 3 Batt Symmetry 4 From internal batteries From area with internal batteries Temperature sensor Temperature Sense 1 NA NA From are...

Страница 29: ...s alarm and digital input monitoring signals are accessible from the controller s rear panel on mini power connector CON1 2 outputs 2 inputs Using the Alarm Interface Card Art 218470 plugged to Smartp...

Страница 30: ...1 2 accessible at any suitable location inside your cabinet The figures show the card s pin out location and terminal block connections Appendix Alarms Monitoring Terminals Pin out Location CON3 CAN1...

Страница 31: ...close or vice versa when a reversed pulse is applied to the coil System Connections CON5 15 pins D Sub female LVD1A 1 LVD2A 2 LVD Common 3 System Voltage 4 System Voltage 5 a Batt Current 1 6 b Batt C...

Страница 32: ...ry Monitor Battery Monitor Monitor Inputs Terminal Block Power LED Lamp green Warning LED Lamp yellow Pin 1 Pin 8 Alarm LED Lamp red Battery Monitor Connections Part 242100 300 FUNCTION SIGNAL PIN OUT...

Страница 33: ...omer Connections 1 5 mm 2 max wire section DIP Switches 5 8 always OFF 1 2 3 4 Input Circuit 1 Input Circuit 2 Input Circuit 3 Input Circuit 4 6 Config Input From breakers and external equipment 3 2 1...

Страница 34: ...Temperature Sense 1 4 3 2 1 5 8 7 6 X Temperature Sense 2 Temperature Sensor 1 Temperature Sensor 2 Tachometer Input 1 Tachometer Input 2 Fan Speed Monitor 1 Fan Speed Monitor 2 Speed Control Output 1...

Страница 35: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 27...

Страница 36: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 28...

Страница 37: ...igital Input 6 X2A Ext Alarm I O Connections X2B Ext Alarm I O Connections Customer connections Mains input terminals To be labeled 8 L1 N L2 N L3 N PE PE 15 Alarm Outputs and Digital Inputs 1 2 3 4 5...

Страница 38: ...E Underwiring MPBB 6pos 3AC CAN1 Smartpack Power CAN bus Interconnections X5 Power output Y7 Power output Y8 Power module 1 PE N L Power module 2 PE N L Power module 3 PE N L Power module 4 PE N L Pow...

Страница 39: ...Quick Start Guide Minipack PS System 356808 103 1v2 2008 10 31...

Страница 40: ...k Valere Gr terudv 8 Pb 2340 Str ms 3003 Drammen Norway Phone 47 32 20 32 00 Fax 47 32 20 32 10 This product is CE marked and complies with all current requirements for relevant standards and directiv...

Отзывы: